Features and Improvements
- Contingency Analysis Tool: Added CriteriaCheckOnce field with RemedialActionElements. Set this to YES if the Model Criteria should only be checked once during the process of applying Remedial Action Elements in response to contingency actions (model criteria is evaluated with TOPOLOGYCHECK, POSTCHECK, or SOLUTIONFAIL status). If the criteria is not met, this action will not be implemented and the criteria will not be evaluated again. The Persistent field is ignored when this is set to YES. The action will not be implemented and the Model Criteria will not be evaluated again for a Model Criteria that is met but the Time Delay is greater than the Time Delays of other actions whose Model Criterias are also met. This option has no impact if the Model Criteria is not defined.