June 29, 2026
Features and Improvements
- Transient Stability: Completed the development of VHVDC_A1 model. It is no longer considered a Beta version and is ready for use.
- File Formats: Fixed several bugs reading and writing line short circuit data to a PWB file. If the line could not be found when loading, the parameters where not being loaded correctly and would produce access violations and a failure of the file read.
- Optimal Power Flow (OPF): During an AC OPF, fast-start commitment and decommitment was being checked upon completion of the very first optimization inner loop. This premature action could bias units to be committed or decommitted too early in the AC OPF iterations, especially when the initial optimization inner loop created more branch violations that had not been initially captured by the LP tableau. This has been changed to ensure that fast-start commitment or decommitment viability is checked only after all other controls and related constraints have reached an overall numerical optimum. In some situations this allows more fast-start units to be committed (or decommitted), ultimately leading to lower OPF system cost.
- Optimal Power Flow (OPF): For fast-start generation units currently with Status = Open, the correct sensitivity values were not being populated into the Linear Program Simplex tableau. This led to situations where a generator unit would not become committed even though it was actually favourable for it to be committed (i.e., it could actually relieve branch violations and reduce the overall OPF system cost). Fast start decommitment was not affected. For fast start commitment, it worked okay for situations where the area/superarea MW constraint or the cheaper cost of a fast start unit necessitated an action. However, prior to this patch, an intially Open fast start unit would not become committed if its cost was the greater than or equal to the cost of other generation units that were currently Closed in its respective area/superarea.
- Transient Stability: For VHVDC_A1, fixed initialization of the Vac1wInt state when operating is islanded mode (OpMode = 1)
- User Interface Dialogs: When scaling loads by Bus, Area, Zone, or Owner and using the Option to "Scale Only AGCable Load", if the present amount of Non-AGCable load is more than the New Value requested, then Simulator will change all the AGCable load to negative values to meet the request. A dialog box message now appears to warn the user that this is occurring.
- Weather: Bug fix to get the TimeStepLoadPWW to work with the HRR files (the error was in the 80m wind conversion).
Bug Fixes
June 22, 2026
Bug Fixes
- Transient Stability: In VHVDC_A1, fixed bug with handling the DC chopper for the Islanded mode.
- Transient Stability: In VHVDC_A1, modified so KVdc2CH will always use the negative of the absolute value of the parameter.
- Transient Stability: In VHVDC_A1, do not allow TId1f and TId2f to be zero.
June 17, 2026
Bug Fixes
- Power Flow Solution: Fixed index out of range error that could occur when displaying VoltageDroopControl objects when only one existed.
June 15, 2026
Features and Improvements
- Available Transfer Capability (ATC) Tool: When determining how many transfer limiters to keep based on number of times Limiting Elements and Contingencies appear during an ATC run, the limiters are now sorted by contingency name and limiting element description to keep consistency between runs done in different instances of Simulator. They had previously been sorted based on internal object pointers. This would maintain a consistent order within a single instance of Simulator, but might make it difficult to compare results from different runs.
- Transient Stability: REPC_D model was writing the MVA Base for the dyd file with the incorrect "mvab=" format. This was fixed and now the mvab will be written correctly.
Bug Fixes
June 8, 2026
Features and Improvements
- Oneline Diagrams: Added right click menu to display injection group object with options: Injection Group Information Dialog, Show Data View, and Open Model Explorer.
- Power Flow Solution: Modified the algorithm for finding Arriving Branches when connecting generators to remotedly regulated buses to expand the grouping of buses near the remotely regulated bus that are connected by low impedance branches. Previously this grouping was restricted to buses connected by branches with impedances below the ZBRThreshold. The grouping is now expanded to branches connected by impedances below 4 times the ZBRThreshold instead. This helps the numerical stability of the power flow solution.
- Transient Stability: Added a new OscType for the PQWave load model. It acts similarly to the Square wave, but instead does a ramp for each square instead.
- Case Information Displays: When first opening a case information display with a large number of columns (>128), but no objects (rows) in the table, the column headers were not updated immediately. This has been fixed.
- Oneline Diagrams: Added support for reading shapefiles with the LAMBERT_AZIMUTHAL_EQUAL_AREA.
- PV and QV Curve (PVQV) Tool: When saving a PV legacy plot to file, file extensions were not automatically being included if they were not specified in the filename selection. This has been fixed and the file extensions are now automatically included if not specified. When saving a JPEG file, an intermediary WMF file was being created. This is no longer needed and shouldn't appear along with the JPEG file.
- QV Curve Tool: On the QV dialog when changing the name of the output file using the Browse button, the filename would not always be changed to the new value. This has been fixed.
- User Interface Dialogs: When attempting to add a three-winding transformer through the GUI and the selected Starbus contained a gen, load, or shunt, an infinite loop of messages indicating that you cannot have gens, loads, or shunts attached to the starbus would occur. This has been fixed.
Bug Fixes
May 29, 2026
Bug Fixes
- Transient Stability: Fixed a bug in which transient stability was looping during multiple contingency run if the transient contingency was using a regular power flow that ALSO was loading an aux file. This bug was fixed.
May 28, 2026
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): In an unusual situation, when deleting a branch connected to a star bus of a three-winding transformer, an access violation or reference notification error could occur. This has been fixed.
- GIC: Fixed bug with writing and reading *.gic files.
- GIC: Updated GIC handling of Earth Resistivity models. Also fixed some bugs and added a GIC Earth Region Set dialog.
- GIC: Minor change so with GIC regions if there are no lat/lon values the fields are blank.
- Transient Stability: Modified how VHVDC_A1 is initialized when KiVac1w = 0. Also fixed bug in derivative of state related to KiIac1w
- Weather: When using the Save to Aux button on a branch options dialog and the branch is a transformer, transformer fields will be included in the aux file.
May 20, 2026
Features and Improvements
- Transient Stability: Adding initial draft of VHVDC_A1
- File Formats: Added ability to read and write from a RAW file the transformer "Load Drop" impedance. These are read into the PowerWorld Line Drop values.
- File Formats: Also modified reading of switched shunts, FACTS, and Bus shunts to clean up writing those back out to RAW version 35 and later which can have IDs with the shunts.
- Oneline Diagrams: When displaying the default font size for a oneline, the value in the dialog is shown as a point size. This value was not being set correctly when using the font size that is specified with the DefDrawOneline object. This has been fixed.
Bug Fixes
May 18, 2026
Bug Fixes
- Oneline Diagrams: When reading and writing display gauge objects to AXD files the width was not being included, this has been fixed as is now included.
- Oneline Diagrams: For display objects added a field, NoZoomValue, that retains the zoom level when the NoZoom field was set to YES. This will allow retaining the proper size when loading a oneline from an AXD file.
- Oneline Diagrams: When saving and loading background text objects from AXD files, use special characters for carriage control line feeds in the text field so that these do not interfere with the format of the file.
- Oneline Diagrams: When loading display objects from an AXD with the option set to not resize the object on zoom, the object size would be set to some undefined value and the object would not be displayed. This has been fixed.
- Oneline Diagrams: In default drawing values for buses when defining the default fields to occupy various positions, the kV voltage field was not identified correctly when saving the default field positions to an auxiliary file. It would show up as a field name of "None". It will now show up as the field name of "Voltage kV".
- Transient Stability: Fixed an initialization error with the REPC_D model that was causing a non flat run.
May 11, 2026
Features and Improvements
- File Formats: When reading/writing a RAW file transformer record with CM=2, the test results are given assuming the open circuit test voltage was the nominal kV of the From Bus or Primary Winding. Previously we had been assuming it was on the Bus records nominal voltage instead. This has been corrected.
May 8, 2026
Features and Improvements
- Oneline Diagrams: Display background objects that are linked to power system objects now have an option in the right click menu when in run mode to show the linked object in the Model Explorer. Background pictures that are linked to power system objects now have options in the right click menu when in run mode to show the linked object's dialog or show the linked object in the Model Explorer.
- Transient Stability: Added ability to read and write the _cmp_perc1 as a load component in the DYD file
- Auxiliary Files (SCRIPT and DATA Sections): Fixed SendToExcel script command that wouldn't produce file not found and directory path not found errors if the name of the workbook did not include a path. This is related to the changed may on April 29, 2026.
- File Formats: The patch used when a PWB file is saved is stored in the file starting with Simulator version 22. This is now shown in the message log when loading a PWB.
- Transient Stability: Code for handling Switched Shunt DYR records which may have an ID or omit an ID string which was added last week was causing an error when reading a user-written FACTS (USRFCT) model such as 'SVSMO3U2'. This has been fixed.
- Transient Stability: Modified warning messages written to the log regarding USRBUS models PLNTBU1 and HPLNTDU depending on the whether the plant models appeared before the auxiliary model that link generator to the plant model.
- Weather: Fixed bug in windchill calculation that I introduced on May 4 patch.
Bug Fixes
May 5, 2026
Bug Fixes
- QV Curve Tool: Fix to ensure option changes on the QV dialog are made with the QVCurve_Options object if the QV dialog is closed immediately after making a change without any additional actions on the dialog
- Transient Stability: There was a reading error of the parameters for the REPC_D when reading from a dyd file. This issue was fixed.
May 4, 2026
Features and Improvements
- Transient Stability: Added reading the Vpllfrz parameter for REGFM_B1 transient model from a PSLF dyd file.
- Transient Stability: Added ability to read/write from a DYD file the REGFM_C1 grid-forming model
- Transient Stability: Added ability to read/write from a DYR file the REPCGFM_C1 grid-forming plant controller model
- Transient Stability: When loading a DYR file if a generator or object referred to by a stability model did not exist, the log message will now start with the word "Missing" instead of "Error".
- Transient Stability: Modified to read and write the CCOMP4A model from a DYR file and treat it as a CCOMP4 model
- Transient Stability: Added ability to read/write the H6E1 and H6E1H governor models from a DYR file and treat it as a H6E model. Also added ability to translate the USRMDL H6E1U to H6E1.
- Transient Stability: Added ability to read ABBSVC2 as a ABBSVC1 switched shunt models. When reading a DYR file, PowerWorld looks to see if a 2-character id string between single quotes is in the model declaration and reads switched shunts appropriately based on that.
- Transient Stability: Added ability to read SWSHNT2 as a SWSHNT switched shunt model. When reading a DYR file, PowerWorld looks to see if a 2-character id string between single quotes is in the model declaration and reads switched shunts appropriately based on that.
- Transient Stability: When reading a REGCAU2 model from a DYR file it is translated to a REGC_A model.
- Transient Stability: Added ability to read the USRMDL BASOELU1 and BASOELU2 and translate it to a BASOEL2 model.
- Transient Stability: Added ability to read and write the DERA1 machine model from a DYR file.
- Transient Stability: Added ability to read various switch shunt models in flexible ways that allow the DYR record to have the ID of the shunt or not. There are 6 standard stability models that come in 2 versions in the DYR Format as follows
* ABBSVC1 and ABBSVC2
* CHSVCT and CHSVCT2
* CSSCST and CSSCST2
* SVSMO1T2 and SVSMO1T3
* SVSMO2T2 and SVSMO2T3
* SWSHNT and SWSHNT2
All of these model names in PowerWorld Simulator will have the first model name listed for PowerWorld's model name. When reading a DYR file,The following are valid headings
123456 'SWSHNT2' '1' 0 9 1.04 2 0.1 0.95 1 0.05 /
123456 'SWSHNT2' 1 0 9 1.04 2 0.1 0.95 1 0.05 /
123456 'SWSHNT' 0 9 1.04 2 0.1 0.95 1 0.05 /
PowerWorld will also interpret a few uncorrect syntax as it is clear what the person creating the DYR file intends, and we have seen these in customer DYR files
123456 'SWSHNT2' 0 9 1.04 2 0.1 0.95 1 0.05 / the ID was incorrectly omitted, but the number of parameters matches, so read anyway
123456 'SWSHNT' '1' 0 9 1.04 2 0.1 0.95 1 0.05 / the ID is included with quotations so it's clear it is an ID - Transient Stability: When reading a DYR, added ability to translate the USRMDL AC11CU1 to a AC11C exciter model
- Transient Stability: When reading a DYR, added ability to translate the USRMDL AC7CU1 to a AC7C exciter model
- Transient Stability: When reading a DYR, added ability to translate the USRMDL AC8CU1 to a AC8C exciter model
- Transient Stability: When reading a DYR, added ability to translate the USRMDL ST6CU1 to a ST6C exciter model
- Transient Stability: When reading a DYR, added ability to translate the USRMDL ST8CU1 to a ST8C exciter model
- Transient Stability: When reading a DYR, added ability to translate the USRMDL OEL2CU1 to a OEL2C OEL model
- Transient Stability: When reading a DYR, added ability to translate the USRMDL UEL2CU1 to a UEL2C UEL model
- Transient Stability: Modified the OEL5C model to include an extra input parameter IFDdolev which is a drop-out level below which the OEL activation logic set it back to inactive. Previously IFDdolev = IFDpulev always, so the same level was used for activating and deactivating. If IFDdolow <=0 then it defaults back to old behavior.
Added ability to read and write the OEL5C model form a DYR file.
Added ability to read a OEL5CU1 USRMDL and treat it as a OEL5C model - Contingency Analysis: Cleaned up the Insert Special right-click drop down menu in the Contingency Analysis dialog. Features on this menu all can be related to a selection that is made in the list of contingencies, except for a few items under a new submenu called "Full Topology Breaker Features"
- Time Step Simulation: Fixed issue in which time step was not correctly returning the wind chill or heat index values. Also these values and relative humidty are now rounded to integers.
- Transient Stability: Fixed a bug with the PSS2C that was causing a small initial movement of the stabilizer during initialization
Bug Fixes
April 29, 2026
Features and Improvements
- GIC: Also changed the GIC Form to allow the uniform electric field to be enter with up to three digits ROD.
- Transient Stability: Added ability to read/write from a DYR file the REGFMC1 and REGFMC1U and translate it to a REGFM_C1 grid-forming model
- Transient Stability: Added ability to read/write from a DYR file the REPCGFMC1 and REPCGFMC1U and translate it to a REPCGFM_C1 grid-forming plant controller model
- Auxiliary Files (SCRIPT and DATA Sections): Modified how the SendToExcel script command interacts with presently open Excel Workbooks to prevent errors and conflicts with Excel.
- Case Information Displays: Modified the Quick Pout so double-clicking to move between buses again works.
- Transient Stability: Fixed a bug reading and writing REPC_D model from a dyd file. We were expecting a bus number before the semicolon. PSLF doesn't put a bus number before the semicolon thus in PowerWorld we will load the REPC_D model to the RegBus Bus.
Bug Fixes
April 23, 2026
Features and Improvements
- Transient Stability: Modified to read/write a REGFM_B1 model from the DYD format
- Power Flow Solution: Fixed an error in the Voltage Conditioning Tool which could occur if a generator in the power flow case was regulating a bus that it could not reach (such as a dead bus)
Bug Fixes
April 22, 2026
Features and Improvements
- Transient Stability: Added new load characteristic models for playing in a variation of the Load P and Q.
* PQWave is allows you to specify a pulsing square wave, triangle wave, or sinusoidal wave for the P and Q of the load
* PlayInLoad is allows you to define a PlayIn structure that has a variation of the load
Both of these models are laying in a scalar function where 1.00 represents the initial MW of the load and the user can define a time-variation of this multiplier. - Transient Stability: Adding ability to read/write the REGFMB1U USRMDL from a DYR file and convert to the REGFM_B1 model. This is then written back to the DYR file as a REGFMB1 record.
April 20, 2026
Features and Improvements
- Oneline Diagrams: When saving a oneline background picture to an AXD file, the image will now be encoded in a field directly in the object record rather than saving a separate file that then needs to be passed around with the AXD.
- GIC: Fixed bug where TimeStepLoadB3D script command would always set the solution type to GIC Only.
- GIC: Removed some commas in column headers for GIC files to prevent problems in CSV files.
- GIC: Improving GICHarm Integrated Tool.
- GIC: GIC
Updated the GICHarm Integrated Tool. Fixed bug in which the *.gic values for transformers were not being correctly exported.
Bug Fixes
April 16, 2026
Bug Fixes
- Scheduled Actions: Changed how MW adjustments in response to Set To/Change By adjustments to Gen limits are logged
- Transient Stability: Fixed use of plant controllers controllers in conjunction with REGFM_A1 and REGFM_B1 grid-forming converter models.
- Transient Stability: Fixed error in REGFM_B1 when Kpv was not zero.
- Weather: Fixed issue with Gen Max MW Wind PFW models in which values were not being set correctly if the weather did not have 100m wind measurements. Also fixed issue in which weather data would not show correctly sometimes on the Gen Dialog.
April 10, 2026
Bug Fixes
- Oneline Diagrams: When loading an AXD file that had been saved using labels identifiers, some object types were not loading back in properly. This includes any display object, field, pie chart, or geodataview that was linked to the following object types: InjectionGroup, Area, Zone, InjectionGroup, Interface, SuperArea, and Owner objects.
- Scheduled Actions: Improved error reporting of Outage CSV files loaded with no data.
- Transient Stability: Added Delete button to the Modal Analysis Dialog to delete all the modal analysis data.
- Transient Stability: Fixed a bug that was preventing using the REGFM_A1 and REGFM_B1 transient models with the REPCA1 and REPCTA1. This was fixed.
- Transient Stability: Removed restrictions inside PowerWorld Simulator regarding REPCA1 and REPCTA1 plant controllers are connected to a particular type of machine model. Within PowerWorld Simulator, there is no difference between the REPCA1 and the REPCTA1 model. If a Pref controller (Torque controller) is defined for the generator, then the plant controller will send the P signal to it, otherwise it will send it to the electrical control (REEC_*). PowerWorld determines this automatically. Older restrictions where only added for ensuring compatibility when writing a DYR file however. When writing out to a DYR file PowerWorld was checking and writing out what is required in that format already, so no need to add restrictions inside PowerWorld.
- User Interface Dialogs: Fixed bug when using any option other than All when selecting the Lines to Process when using the tools to determine the path distances between buses or shortest path between buses tools.
March 25, 2026
Features and Improvements
- Scheduled Actions: Updated how OneAtATime outages are loaded from PowerWorld Outage CSV files -- rather than simply creating one action for the most limiting element at load time, actions for each element in the group are created, and disabled aside from the one selected element's action.
- Oneline Diagrams: Minor edit regarding fontcolor defaults
- Optimal Power Flow (OPF): When reopening a case with solved OPF/SCOPF results, and that case had been earlier saved while viewing the full tableau, the basis matrix or full tableau would not display correctly. Users would have noticed incorrect sensitivity values for some columns corresponding to each control in the linear program. This was corrected.
- Scheduled Actions: Adjusted when ScheduledAction Action field is disabled to indicate when ActiveAllow is set to NO
Bug Fixes
March 19, 2026
Features and Improvements
- Oneline Diagrams: Added an option to show Line Shunts on Branches, Transformers and Series Caps. If the branch has 2 segment or less the Line Shunt will be placed in the middle of the segment.
* If the branch has 3 or more segment the line shunt will be placed at the end of the segment in the From Bus and the start of the last segment in the To Bus.
* If the branch has 1 segment then line shunts will be placed at 10% and 90% of the segment.
* If the branch has 1 segment the size of the Line Shunt will be 10% of the segment, and if the branch has more than 1 segment the size of the Line Shunt will be 0.25% of the line segment. The width of the Line Shunt will be half the length of the line shunt.
* If the Line Shunt MVARs total is greater than 0 the line shunt will display a capacitor symbol and if the line shunt total is less then 0 it will show a reactor. Zero total MVARs will result in no line shunt shown on the branch. - Optimal Power Flow (OPF): For constraints that have both upper (positive) and lower (negative) limits in the OPF/SCOPF, the Lagrange multipliers for each constraint, Lambda values being displayed in the user-interface and returned through AUX script or data sections were the absolute value of the actual Lambda value calculated by the Simplex linear program. In keeping with the convention that the Lambda for each constraint is the incremental price for increasing the flow on that constraint by 1 unit, both positive and negative Lambda are meaningful. A Lambda of zero means that the constraint is within limits, and a non-zero lambda means at or exceeding limits. So if an interface A is at +250 MW and is exceeding a +234 MW positive limit, then the marginal price is +1000. When an interface B is at -150 MW (since it was monitored in both directions) and is exceeding a -123 MW negative limit, then the marginal price is -1000. Increasing flow by 1 MW on interface B (from -150 to -149), will incur a price of -1000, because increasing by 1 MW lessens the degree of violation, hence a reduction of 1000 in price. the values reported as the marginal cost reported for lines, interfaces, etc are now consistent with this.
- Security Constrained OPF (SCOPF) Tool: Contributions to bus MW Marginal Cost from contingency interface constraints was wrong due to a sign error. This has been corrected.
- Security Constrained OPF (SCOPF) Tool: The loops in the DC and AC SCOPF were slightly different with respect to the criteria to continue including more contingency violations into the LP simplex tableau. In AC SCOPF, having both the tableau constraints within the tolerance and having no further control changes would no longer include new contingency violations into the tableau -- the idea being, with the worst violations already included, there was no additional control range available to make a difference to the remaining contingency violations that were not included. In contrast to this, in the DC SCOPF having the tableau constraints within the tolerance was being checked, but having no further control changes was not being checked. This would result in many more constraints to be included in the tableau, but all those gave insignificant control changes. The DC SCOPF termination logic has now been changed to match that of the AC SCOPF. The AC and DC SCOPF dispatches would be the same as before, The improvement comes in the explainability of the results shown in the contingency violation table that would now be commensurable across both DC and AC SCOPF methods.
Bug Fixes
March 9, 2026
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): Fixed a bus on REPC_D model or similar bus transient models that was preventing the use of Advanced Filters with the objects.
- Optimal Power Flow (OPF): When solving OPF/SCOPF and using the option to "Balance Marginally Similar Controls", there were situations when the simplex linear program would be redone an excessive number of times triggered by balancing of decision of variables, and this caused the OPF/SCOPF to run for a very long time but with very little control changes.
March 6, 2026
Features and Improvements
- Oneline Diagrams: Modified Default Drawing Values so that a font color can be specified for different Nominal voltage kV levels with various objects. Previously you could specify a Font Size that was different by voltage level, but all inserted fonts were the same color.
- Auxiliary Files (SCRIPT and DATA Sections): A change that was made in the 1/26/26 patch could affect how branches are found when identified by bus name_nomkV. This bug has been fixed.
- Oneline Diagrams: Fixed the dialog box when choosing on a oneline to Auto-Insert -> Reset Stub Locations. It was showing a "Do not Insert Pie Charts" check box which it should not have been
- Power Flow Solution: When two phase shifters are in series, and one is already at a limit, it caused the other phase shifter to back off its limit and reattempt to regulate the flow. More generally, for any phase shifter, backing off a phase limit is only desirable when the phase min (or max) limit is exceeded, as well as the actual flow is greater (or less) than the regulated flow middle. The observed issue was that phase shifter oscillations led to a phase shifter regulation error message for the DC power flow, even though the DC power flow had already reached a good solution. This modification prevents an unnecessary error being produced during a DC power flow solution.
- Security Constrained OPF (SCOPF) Tool: When solving SCOPF/OPF with interfaces monitored in both directions, the corresponding entries in the simplex linear program were incorrect. This led to odd enforcement of interfaces that were monitored in both directions. This is fixed.
Bug Fixes
March 2, 2026
Bug Fixes
- Optimal Power Flow (OPF): Reverting a portion of the software patch from February 16, 2026 that deals with incorrect marginal prices during OPF/SCOPF shown for certain interfaces being monitored in both directions and limiting/violating in the negative direction. This change incorrectly affected branch flow constraints. Users will have noticed incorrect OPF/SCOPF dispatches if they had installed a patch dated between Feb 16-23, 2026.
- Security Constrained OPF (SCOPF) Tool: Reverting a portion of the software patch from February 16, 2026 that deals with incorrect marginal prices during OPF/SCOPF shown for certain interfaces being monitored in both directions and limiting/violating in the negative direction. This change incorrectly affected branch flow constraints. Users will have noticed incorrect OPF/SCOPF dispatches if they had installed a patch dated between Feb 16-23, 2026.
February 23, 2026
Features and Improvements
- Case Information Displays: Modified the Send to Excel feature so that the list of presently open Workbooks will expand horizontally as the dialog is resized. This allows the user to see the full filename for workbooks with very long filenames. Also modified so if the list of present Worksheets is very long, then a scroll box will appear so that the dialog still works.
February 19, 2026
Features and Improvements
- Scheduled Actions: Updated notes added to Actions that adjust MW output to respect limits
- File Formats: Simulator can now read malformed RAW v34 and newer files that contain whitespace between the value and the comma delimiter.
- Oneline Diagrams: Corrected column header for Default Drawing Values for Area, Zone, and Super Area objects. Width mistakenly showed ID1.
- User Interface Dialogs: Generator ramp rates are available fields that are no longer used in any Simulator tools but could be set by a user to keep track of this information. When editing a generator through the generator dialog in either Edit or Run mode, these fields would be set to 0 wiping out any data that may be have set. This has been fixed so that this information is retained.
Bug Fixes
February 18, 2026
Bug Fixes
- General: Fixed an issue that caused TransLineCalc to not run for version 24.
- Transient Stability: For the BASOEL2 model, when OET1 = 0.000 an oscillation of a timer could occur. This has been fixed.
February 16, 2026
Bug Fixes
- Security Constrained OPF (SCOPF) Tool: Bug fix for interfaces with negative MW limits that are used to monitor flows in the reverse direction when an interface is set to monitor both directions. Violated interfaces for contingencies were not being included in the proper sequence, along with the right-hand-side entry for the simplex tableau being incorrectly calculated. The marginal price results were incorrect, along with affecting the overall convergence of the SCOPF outer loop.
- Transient Stability: Fixed an error in storing Snapshots for cases that had definite time load relays.
February 12, 2026
Features and Improvements
- Transient Stability: Changed default parameters of PERC1 to Kvq = Kvp = 0.000 and Kdroop = 0.000.
- User Interface Dialogs: When inserting a new Load Object, an access violation was occurring when opening the Load Dialog. This bug was introduced in the February 10, 2026 patch related to load benefit curves.
Bug Fixes
February 11, 2026
Features and Improvements
- Transient Stability: Modified how the PERC1 and LDEV1 models initialize the value MvarInit when used as a stand-alone model. Previously the QPRatio was ignored for a stand-alone model, but this has now been changed so MvarInit = QPRatio * MWInit always for this model. With this change, any mismatch in Mvar between the initial condition Mvar will be made up by a internal parameter IqExtra that is calculated during initialization. See the help documentation on PERC1 and LDEV1 for more information.
- Security Constrained OPF (SCOPF) Tool: The input parameter in SCOPF for "Maximum Number of Contingency Violations Per Element" was being exceeded when deciding which interfaces violations to keep during the SCOPF, along with the same contingency-interface being duplicated in the list of SCOPF Contingency Violations list. This also had an impact on how the linear program solved, which led to poor dispatches in certain parts of the system. This has been corrected. Related to this, but not impacting the solution quality, the "Error" value reported for interfaces with a "negative" or lower limit, was displayed incorrectly. This has also been corrected.
Bug Fixes
February 10, 2026
Bug Fixes
- Optimal Power Flow (OPF): When moving Load MW values in the OPF or SCOPF solution and choosing the option to maintain a constant power factor, we have modified it so that the MW can not be decreased to a value lower than half the MVA convergence tolerance. This is done so that the load will not be set to 0.0000 MW and 0.0000 Mvar because this causes the solution to lose information about the Q/P ratio.
- Power Flow Solution: When changing the monitor direction of an Interface needed to update structures related to calculating contingent interface flows. We now ensure this is done.
- Security Constrained OPF (SCOPF) Tool: When moving Load MW values in the OPF or SCOPF solution and choosing the option to maintain a constant power factor, we have modified it so that the MW can not be decreased to a value lower than half the MVA convergence tolerance. This is done so that the load will not be set to 0.0000 MW and 0.0000 Mvar because this causes the solution to lose information about the Q/P ratio.
- Sensitivity Calculations: When using the Monitor Direction = "TO -> FROM" for an Interface, in situations where the outage elements within the Interface definition resulted in isolated buses, the Shift Factor calculation for an interface could show incorrect values at the isolated buses. This has been fixed.
- Transient Stability: Fixed a bug with the "Re-evaluate to get Limit Monitor Violations". When monitoring Buses, if the bus was disconnected during the simulation it was reporting violations for those buses. When you run transient stability, buses that are disconnected are not monitor for limit violation purposes. Now this was fixed for the Re-evaluate after you already have results in RAM or in Hard Drive. However, for Bus objects violations, if using results in RAM, make sure to also have Bus Status results in RAM because if not, violations will ALSO be shown for disconnected buses. For Hard Drive Bus objects violations, nothing else needs to be done and the violations will be only reported for connected buses.
- User Interface Dialogs: When opening the Load Dialog box, if the load did not presently have any Benefit Curve points, the table on the OPF Load Dispatch tab of the dialog would be populated with entries of 0 MW and a 10000 $/MWh benefit. Click OK would then add this 0, 10000 marginal benefit curve point to the case. This was confusing and has been removed so that the table populates to empty instead which is the same as the generator dialog bid curve points.
February 6, 2026
Bug Fixes
- Transient Stability: When saving using TSGetResults script command or TSGetCongencyResults automation server function, the list of object fields (signals) requested would return fewer than the number of signals expected. This would happen when the signals corresponding to towards the end of the ordered list of object fields would have not been set to save in Results Storage to RAM or HD. This has been corrected to always return the same number of signals as requested.
February 4, 2026
Bug Fixes
- File Formats: When saving to a PTI RAW file for version 34 or greater and saving substations, an access violation could result if a three-winding transformer did not include a tertiary winding. This has been fixed.
- Oneline Diagrams: Fixed error resulting in access violation when attempting to save a oneline diagram as a Shapefile.
February 3, 2026
Bug Fixes
- File Formats: Fixed a bug where reading or appending 3 winding transformers would still try to create an object even if the primary and/or secondary bus didn't exist in the case. This partial data was then creating hangs around and caused wacky problems later.
- PV and QV Curve (PVQV) Tool: The 12/19/25 patch for Simulator version 24 has a fix for access violations that could occur when deleting objects that are monitored with PV and QV quantities to track. This fix resulted in only one field type being monitored for each type of object monitored. This problem has been fixed so that all field types are now monitored for each type of object that is being monitored.
- Transient Stability: When using transient limit monitors for Bus objects and also using the Integrated Topology Processing add-on, there could be access violations that prevented the simulation from running. This has now been fixed.
- Transient Stability: Simulator has for many years allowed a Load object to be assigned 2 load models simultaneously
1. A model with dynamic states like MOTORW, which has a fractional portion of the load
2. A second model that was algebraic only and covered the "remainder" of the load (WSCC)
The code around this concept always assumed the user would never specify two models that had dynamic states simultaneously. This patch fixes a bug when this is seen which resulted in the load being double-counted. - Transient Stability: The PERC1 model can be used as one of the components referred to by a CompLoad model. When this is done with multiple components, then the parameter QPRatio is used to assign Mvar to the PERC1 model and then any extra Mvars are modeled as part of the distribution system equivalent. If however the CompLoad model has only ONE component assigned and it is a PERC1, then it should behave the same as if the load had a stand-alone PERC1 model and default back to ignoring the QPRatio and assigning MVar according to the flow solution Mvar value. This patch changes it so that special treatment is used if the PERC1 is the only component in the CompLoad model.
January 29, 2026
Features and Improvements
- Integrated Topology Processing (ITP): RT_Study_Options variablename SavePreservesCB renamed to SaveCTGsAndRelated. This field has always meant to specify whether or not to save contingencies. Old legacy name is still supported.
- Bus View and Substation View Onelines: Cleaned up BusView slightly when showing multiple parallel paths and showing a second tier of buses.
- Data View: Minor edit for layout of the DataView dialogs to ensure the group boxes maintain the thin outline
- Distributed Computation: Fixed a bug where DistCTG was sometimes not properly handling files from remote instances when saving results to hard drive.
- File Formats: Added log messages when reading duplicate SPMEAS records from Areva hdbexport file. These are used to create ModelResultOverride objects and the last record read is the one that is kept.
- Integrated Topology Processing (ITP): When using options to save consolidated cases and choosing to not save contingencies, no contingency related objects will be saved.
Bug Fixes
January 26, 2026
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): When identifying branch objects by secondary key fields in auxiliary files and multiple buses existed with the same NameNomkV, it was possible that branches could not be found because we were only checking branch connections to the first bus found with a given NameNomkV. Now we make an attempt to find a branch by looking at any buses with the same NameNomkV at either terminal of a branch. Users should always be careful when using secondary key fields with objects, because they may not represent a unique object.
- File Formats: Fixed a bug where blank lines and repeat lines were being written to PTI GCAP files containing generator reactive capability curves.
- Transient Stability: Some corrections to Exciter models AC10C, AC11C and ST10C with the coordination of the SWOEL, SWUEL, and SWLIM logic.
Bug Fixes
January 26, 2026
Features and Improvements
- Case Information Displays: For case info row metrics, the histograms are now implemented. Also, the dialog now shows the transpose of the selection (e.g., if one row is selected the dialog shows it as a column); this allows the row to easily be sorted and/or plotted.
- Auxiliary Files (SCRIPT and DATA Sections): When loading AUX Export Format Descriptions from an auxiliary file, errors could be displayed in the message log if comments are added to the ends of lines in SUBDATA sections. The description would be created correctly, but the error message was misleading. This has been fixed.
- Case Information Displays: Fixed an issue that could cause spurious access violations on dialog boxes containing Case Information Displays.
- Case Information Displays: Fixed bug when manually setting the for DC line alpha and gamma angles. When editing manually or loading from an AUX file the proper conversion from degrees to radians was not done. This shouldn't have much of an impact since alpha and gamma are almost always calculated internally.
- Distributed Computation: When running Distributed Transient Stability, set the Processed field to YES for a contingency that has just completed instead of setting the Solved field to YES. The Solved field will be set appropriately after all contingencies have completed.
- Distributed Computation: Added a check when Distributed Computing is kicking off to ensure there are any Distributed resources configured; if not, the run is ended before a Windows System Error is triggered.
- File Formats: When appending a case with a PWB file that contains three-winding transformers, use the primary, secondary, tertiary, and circuit ID as key fields. If a transformer already exists that matches this the existing transformer will be updated with the new parameters in the file. Previously a new three-winding transformer was created with a new circuit ID and this was causing various access violations.
- GIC: Fixing a memory leak when running repeated GIC solution.
- GIC: Fixed issue in which the GIC line sensitivity value was being returned as blank.
Bug Fixes
January 21, 2026
Bug Fixes
- Contingency Analysis: Allow device filters for CTG auto insert options to be cleared by entering blanks in aux file data and script commands.
- Distributed Computation: An access violation could occur when starting Distributed Transient Stability if the case contained ContingencyPrimary results. This has been fixed.
- File Formats: Fixed an issue that could cause out of memory errors when saving extremely large cases or other large files.
- PV and QV Curve (PVQV) Tool: When using consolidation and saving archive cases with PV analysis, contingencies are not saved because the definitions can be different than how they are originally defined. Now primary contingencies are no longer saved as well.
- Transient Stability: In stability, PowerWorld was using a generator's internal transformer off-nominal tap ratio StepTap even if the internal step-up transformer's StepR and StepX where both zero. We have now changed it so that tap ratio is ignored if both StepR and StepX are zero. We were seeing strange results in MMWG cases which had a StepTap set as 0.205 with StepR=StepX=0.0
January 8, 2026
Bug Fixes
- Case Information Displays: When defining a filter on a case information display, PowerWorld did not consider this enough of a change to show the "DataGrid" in the list of case information customizations. This meant you could not clear out the Filter using script commands like SetData(DataGrid, [Filter], [""], All); Now specifying a filter will be considered a customization.
- PV and QV Curve (PVQV) Tool: When logging branch or interface violations with the PV tool and the object being logged is deleted, an access violation could result. This has been fixed.
December 22, 2025
Bug Fixes
- Optimal Power Flow (OPF): When including thousands of contingent interfaces to be enforced during an OPF, the OPF algorithm would include a very large number of violated contingent interfaces into the linear program tableau. This would make the basis very large and significantly slow down the calculation of the inverse of the basis. Including all contingent interfaces was unnecessary, and the improvement in this patch implements a way to filter and include only those contingent interfaces that have a non-zero contingent MW flow contribution. This allows users to specify a very large number of interface-constraints and still arrive at a tractable OPF solution. This improvement was tested with 43,000 interface constraints in an OPF, where the tableau would previously include 7,500 constraints, and that was filtered down to around 500 constraints. This 15-fold reduction in the size of the basis matrix resulted in a 3000-fold (order n^3) reduction in the time needed to calculate the basis inverse in the inner loop. A user had reported that the OPF kept running but it was just taking a really long time to solve.. With this improvement the test case OPF solved in about 165 seconds. Otherwise, it would have probably terminated after around 6.5 days!
December 19, 2025
Features and Improvements
- Transient Stability: Added special processing when writing out a DYR file so that any LHVRT or LHFRT models are written out as groups of VTGTPAT and FRQTPAT models.
- Transient Stability: Added the ability to read and write the ESST10C model from a DYD file. This translates to an ST10C model.
- Transient Stability: Cosmetic changes inside the PowerWorld user interface to make it clear how REPC_B, REPC_D, LHFRT, and LHVRT models are translated into groupings of other model types when written out to a DYR file.
- Transient Stability: Added extra sets of default input parameters for the LHVRT model. The primary default remains all zeros indicating no tripping is done so the user must populate with generator specific tripping parameters. Two new sets have been added as follows
1. MAY trip region for IEEE 2800 Table 11 with Aux Load Limitations
2. MAY trip region for IEEE 2800 Table 12 without Aux Load Limitations
It should be noted that these IEEE 2800 standard tables represent Voltage/Time settings at which an inverter-based resource MAY trip, however the IEEE 2800 standards does not say that the generator MUST trip. By adding an LHVRT model with these input parameters then you will be creating a generator that will always trip in these Voltage/Time regions. Please confirm these are appropriate settings for your generator.
- PV and QV Curve (PVQV) Tool: When deleting the objects that are monitored with tracked quantities for PV or QV analysis, an access violation could result. This has been fixed.
- PV and QV Curve (PVQV) Tool: For critical PV scenarios the buses with the maximum MW and Mvar mismatches are reported. Prevent access violations if these buses are deleted.
Bug Fixes
December 11, 2025
Features and Improvements
- Transient Stability: Added code with a Distributed Generation model which specifies a FilterPmin, FilterPQMin, and FilterVmin as filters of when to use the specified Distributed Generation model. When loading a _cmpldw2 model, the distributed generation model created from any dgpv or dgder_a models inside the modulate CompLoad will use the Pmin of the load model divided by 5.
- General: Prior to this patch, DC lines could be defined inside the user interface with duplicate Num ID when their Rectifier and Inverter bus numbers were reversed. This has been changed such that these two objects cannot be simultaneously present.
DCTransmissionLine '615600' '615353' '1'
DCTransmissionLine '615353' '615600' '1'
Instead, a new Num ID must be chosen for the later object, such that:
DCTransmissionLine '615600' '615353' '1'
DCTransmissionLine '615353' '615600' '2'
This change does not impact reading from an AUX file, because this was already being enforced. However, this change does impact defining a DC line object from the user interface, and also while reopening a PWB file that might have duplicate Num IDs.
- Optimal Power Flow (OPF): In OPF, the island constraint equation was not being formed correctly leading to oscillating dispatches in the OPF. In the equation, the scheduled export quantity for the island was being entered in MW, instead of per-unit. This caused the island equality constaints to be off by a factor of the system MVA base, hence giving a bad OPF solution.
- Power Flow Solution: Bug fix for the DC tie line list for areas, zones and super areas that was not being populated correctly when there were 2 DC lines defined across the same two AC buses, with the same Num ID, but with the Rect/Inv buses transposed. This would affect the ACE calculation and cause the power flow to shift upon resolving.
- Transient Stability: It was possible to get access violations when running distributed power flow contingency analysis and monitoring transient stability models. This has been fixed.
Bug Fixes
December 9, 2025
Features and Improvements
- Bus View and Substation View Onelines: Modified BusView to accommodate 6 fields for Generator, Load, Shunt, and FarBus. The display gets very crowded as the layout will expand vertically when moving past the previous 3 for Gen/Load/Shunt and 4 for FarBus.
- User Interface Dialogs: Modified Quick Power Flow List to handle 8 and 9 digit bus numbers.
December 5, 2025
Features and Improvements
- Transient Stability: In TS the Transient Contingency Elements case info display now supports filtering. Also contingency elements can now have an "Object Value" and "Object Value Description" fields which provide information about contingency pertinent object values. For example, for opening a generator this fields show's the generators current MW output.
- Integrated Topology Processing (ITP): The maximum bus mismatch fields available with the PWCaseInformation object will now be populated regardless of the solution options for topology processing and solving islands. This additionally fixes issues that the 12/2/25 patch was trying to fix by not showing these values.
- Transient Stability: When writing out aggregate _cmpldw models to a DYD file we now properly write a reference to a to cmp_der_a models if they have been specified
- Transient Stability: When writing out aggregate _cmpldw2 models to a DYD file we were missing the fraction assigned to the cmp_der_a model. This has been added. The reading of these records was always working correctly.
Bug Fixes
December 2, 2025
Bug Fixes
- Case Information Displays: If a case information display has an advanced filter in use and you right-click on the case information display to edit the advanced filter, and then delete the advanced filter an access violation could occur. This has been fixed.
- Integrated Topology Processing (ITP): The maximum bus mismatch fields available with the PWCaseInformation object will now be blank if using topology processing and the case is not consolidated or using the option to Evaluate Power Flow Solution for Each Island. The way these values are reported with the PWCaseInformation object do not make sense in these situations.
- Integrated Topology Processing (ITP): When using the option to close breakers to energize switched shunts, set the voltage at the newly energized side of the closed breakers to match the energized side so that mismatches calculated after the case is deconsolidated will make more sense. When breakers are closed the superbuses change once the case is deconsolidated, and if the voltages are not updated, the mismatch at buses where switched shunts were closed would be off by the amount of the shunt output.
November 19, 2025
Bug Fixes
- General: When opening the Filter dialog and coming back to it after navigating to another program, it was possible for an access violation to occur. This has been fixed.
November 17, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Modified the 3 script commands to have a new optional YES/NO parameter called AllowPartiallySupportedCTG which allows the creation of an interface from a Contingency definition even if some of the ContingencyElement actions are not supported in an interface definition. Previously we would just not create an interface. Setting this option to YES will create actions that are supported and simply ignore other actions.
InterfaceAddElementsFromContingency("InterfaceName, "ContingencyName", AllowPartiallySupportedCTG)
ATCCreateContingentInterface(filter, AllowPartiallySupportedCTG);
CTGCreateContingentInterfaces(filter, MaxOption, AllowPartiallySupportedCTG); - Available Transfer Capability (ATC) Tool: Added a new option for right-click menu on TransferLimiters objects to "Create Contingency Interface for Selection Only Partially Support". In the past when doing this on a contingency which contained actions not supported in an interface, then Simulator would never create an interface. Using this option allows you to create the interface and any unsupported actions are ignored.
- Contingency Analysis Tool: Added a new option for right-click menu on ViolationCTG objects to "Create Contingency Interface for Selection Only Partially Support". In the past when doing this on a contingency which contained actions not supported in an interface, then Simulator would never create an interface. Using this option allows you to create the interface and any unsupported actions are ignored.
- Simulator Automation Server (SimAuto): Modified the SimAuto OpenCase command to ensure it properly parses Linux-style paths (with / characters). This has inadvertently changed to always assume Windows style paths. We highly recommend that users making use of Python use the command to normalize paths to Windows however. This call in Python is
NewPath = os.path.normpath(oldpath_might_have_linux_paths)
Bug Fixes
November 13, 2025
Bug Fixes
- QV Curve Tool: When renumbering a bus and QV tracked quantities exist, update the sort on the list to match the new bus numbers. This ensures that any inserts into the list of new results are done in a sorted order.
- Transient Stability: There was a bug when opening and closing an injection group in transient stability. The solution was not showing the correct results even when the generators and load were opened or closed. This issue now is fixed and the results will match the opening and closing of the individual generators or loads.
November 11, 2025
Features and Improvements
- Transient Stability: Added the ability to insert transient contingency events using TimeInCycles as a secondary key field using an aux file or copy/paste from Excel. Now the list of secondary key fields is TimeInCycles, Object, Action, and Contingency. Remember that to use secondary keys fields you must omit the primary key field Time.
- Transient Stability: Added special handling in the REPC_D model so that if all Kw terms for specified Control Devices are negative, then Simulator will initialize the output multiplexor control assuming that downstream generators are receiving a voltage signal. This will change the way that Qref0 is calculated as it will be the average of voltage signals be sent to downstream generators at initialization. Also Kw terms will be ignored (treated as 1.0) then. This allows modeling of a plant control that sends voltage reference signals instead of reactive power reference signals.
- Transient Stability: In Transient Stability, validation errors for torque controller, pitch controller and aerodynamic models have now been changed to warnings, for situations when these are not compatible with the upstream model.
Bug Fixes
November 7, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Added script command CTGSkipWithIdenticalActions. This will set the Skip field to YES for any contingencies with identical actions as another contingency. Only contingencies that originally have the Skip field set to NO will be processed. The first contingency with the lowest name alphabetically will not be set to skip. Messages are added to the log detailing which contingencies have been set to Skip = YES.
- Transient Stability: Fixed error reading PWB and RAW files in related to cases that have FRQTPAT, FRQDCAT, VTGTPAT, and VTGDCAT. This bus was introduced in the November 5, 2025 patch
Bug Fixes
November 6, 2025
Bug Fixes
- Case Information Displays: Fix a bug regarding the Balancing Authority (BA) Number shown in the Bus Table and every time the BA number of the bus was used in Model Explorer. it was giving the wrong BA number. That bug is now fixed.
November 5, 2025
Bug Fixes
- Power Flow Solution: Removed the option "Ignore Phase Shift Angle Effects" from the DC options on the DC Approximation portion of the dialog.
- Transient Stability: PSSE uses a model instance integer value as a key field on transient stability models such as FRQTPAT, FRQDCAT, VTGTPAT, and VTGDCAT. These model instance integer values are globally unique in PSSE, across all such model instances and types. Prior to this change, the model instance integer was only unique in conjunction with the generator instance and model type. This has been changed so that when reading or writing to DYR files PowerWorld ensures they are unique globally as well.
November 4, 2025
Bug Fixes
- General: When fixing the bug yesterday related to the log window embedded in the main container window, we introduced a bug when closing most other dialog boxes. This has been fixed.
November 3, 2025
Features and Improvements
- Time Step Simulation: For the Time Step Simulation added script commands for optionally only loading pww data within a specified geographic rectangle.
- Transient Stability: Modified Stability to add a new option to not break the timestep when doing user defined events, though this option is not used by default. When using this option if a time step of 0.005 seconds is used an a TSContingencyElement action is specified to occur at 0.007 seconds, then because we are NOT breaking up a time step, the action will instead occur at the next time step after 0.007 seconds and thus at 0.010 seconds.
- General: Fixed Case Cleanup Dialog bug in which it wasn't working with pwb files with size great than 2.1 GB (the 2^31 - 1).
- General: Fixed an access violation that occurs when the log window is set to be embedded in the main window instead of staying on top.
- Transient Stability: The Te parameter for REGC_B needs to be validated and autocorrected to a factor of the timesteps used in the simulation, just like all other time constants are autocorrected. Without this validation step, small values of Te, and even with a no disturbance transient simulation, might have prematurely aborted the simulation with a message of excessive value for a state variable. This was check was missing and now has been added.
Bug Fixes
October 30, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): DiffCaseWriteBothEPC, DiffCaseWriteNewEPC, and DiffCaseWriteRemovedEPC script commands all have new optional parameter UseDataMaintainer that will use Data Maintainer filtering for including objects in the saved files when set to YES. By default this parameter is NO, which will ignore Data Maintainer filtering. Script commands now have the following parameters:
DiffCaseWriteBothEPC("filename", GEFileType, UseAreaZone, BaseAreaZoneMeetFilter, Append, "ExportFormat", UseDataMaintainer);
DiffCaseWriteNewEPC("filename", GEFileType, UseAreaZone, BaseAreaZoneMeetFilter, Append, UseDataMaintainer);
DiffCaseWriteRemovedEPC("filename", GEFileType, UseAreaZone, BaseAreaZoneMeetFilter, Append, UseDataMaintainer);
- File Formats: When reading in RAW files in Version 24 we were always translating any Gen, Load, or Shunt 2-character IDs to an uppercased version of those IDs. This didn't harm anything, but is not necessary, so we have removed this.
- File Formats: When writing out RAW files, Simulator has always written out Load 2-character IDs as an uppercased version of those IDs. This is not necessary so we have removed that from exports.
Bug Fixes
October 29, 2025
Features and Improvements
- Transient Stability: Added new "Power Electronic Reconnecting and Ceasing" (PERC1) load characteristic model.
- Transient Stability: Fixed an error with transient model OEL5C translation to PSLF dyd file. the parameter SW1 was set incorrectly in the dyd file. Now the SW1 parameter will be set to the correct parameter based on the value in PowerWorld. In PowerWorld OEL reference logical switch 1 (1 = Position A, 2 = Position B) but in PSLF OEL reference logical switch 1 (0 = Position A, 1 = Position B).
Bug Fixes
October 28, 2025
Bug Fixes
- Contingency Analysis: For contingency actions that perform InjectionGroup Set/Change MW values by opening generation or load, additional WhatOccurredDuringContingency entries show the specific generator and loads changes that have occurred with the action. It was possible for these entries to be listed multiple times. This has been fixed.
October 27, 2025
Bug Fixes
- Power Flow Solution: In some rare situations if a system slack bus is disconnected, an access violation could occur. This has been fixed.
October 23, 2025
Features and Improvements
- Transient Stability: Added the ability to load a picture to the Background of a Transient Plot. There is also an option "Back Image Inside" that if checked the image will be added inside the X and Y axis of the plot. If not checked it will be loaded in the entire plot panel.
- Available Transfer Capability (ATC) Tool: No longer exclude contingencies in ATC that completely isolate the source or sink. Modifications to ATC to include the impact of isolating a source or sink participant in OTDF calculations have been made in recent patches and ignoring the contingency completely is no longer necessary.
- General: When deleting a Line Shunt, transient stability contingencies containing actions for the line shunt were not being deleted. This could cause access violations. This has been fixed.
Bug Fixes
October 17, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Added a new Transient Script command: TSClearModelsForObjects(Object, Filter); The Object parameter is required while the filter is optional. This script will remove the transient stability model of the desired object/objects.
- Transient Stability: Added a feature on the Auto Insert Transient Stability contingency dialog to indicate whether to add 1 Open action of 2 actions (Open From and Open To) when adding actions to open branch objects. Previous it would always add 2 commands.
- Transient Stability: Added a feature on the Auto Insert Transient Stability contingency dialog to perform a number of Reclose Attempts and then an interval between the reclose attempts. In the past the general process was to add a fault and then open event. Consider an example: Event Time = 1.0 second; Event Duration = 0.1 seconds; Reclose Attempts = 2; Reclose Interval = 1.90 seconds. This will results in a transient contingency that does the following.
1.00 Fault
1.10 Open branch
3.00 Close branch an interval later (note: the fault will still be there)
3.10 Open branch again
5.00 Close device (attempt #2)
5.10 Open Branch
October 15, 2025
Features and Improvements
- Contingency Analysis Tool: Added a new field to the LimitViol and ViolationCTG objects called MWDirection. For Branch MVA or Branch Amp violations, this field will show either FROM -> TO or TO -> FROM indicating the MW flow direction relative to the branch object's from and to bus designation.
October 10, 2025
Features and Improvements
- Model Explorer: Modification to captions for Machines, Governors, Exciters, and Stabilizers in the Model Explorer. They now say
Gen Exciters (Electrical Control)
Gen Governors (Mechanical Control)
Gen Machines (Converters)
Gen Stabilizers (Wind Pitch) - Transient Stability: Modified the user interface in places where we are listing Exciter, Machine, Governor, or Stabilizer models so that there are folders grouping them by sub-class. For example, the governor model type list will show Hydro, Gas, Steam, Wind, and Other folders. The list of models is getting very long, so some folders for the listing are very helpful.
- Auxiliary Files (SCRIPT and DATA Sections): TimeStepSaveFieldsSet now works correctly with the filter set to SELECTED.
- File Formats: Fixed a bug writing 3 winding transformer records where an extra single quote was being written to the long name, which messed up being able to read the RAW file into PSS/E or back into Simulator
Bug Fixes
October 2, 2025
Bug Fixes
- Transient Stability: Fixed transient branch relay models LOCTI, TIOCR1, TICORS and TIOCRSRF Time Inverse Over Current Relays. The bug was that the Timer was starting at the time the current was higher than the pickup limit but was not checking if the current was in the correct direction. The current direction is set by the direct parameter. Now the timer will start ONLY if the current is higher than the pickup value AND in the correct direction.
October 1, 2025
Bug Fixes
- Available Transfer Capability (ATC) Tool: When running ATC an access violation could occur if using a Super Area as a Seller or Buyer and any conflict occurs between the Seller and Buyer being in different islands or having no online participants.
- QV Curve Tool: Changed the name of the variable name for a QVCurve called "CaseName" to instead be "Contingency". Simulator will still read the old variable name, but we will now always write out "Contingency" from now on
September 22, 2025
Features and Improvements
- Transient Stability: Added a new load characteristic models names LDEV1 which represents the EPRI model first introduced in November 2022 in EPRI report 1-116982 entitled "A Positive Sequency Model for Aggregated Representation Electric Vehicle Chargers". The model is appropriate for representing any loads that interface with the AC power system using power electronic converters. This would include such as Electric Vehicle Chargers, Computer Data Centers, large Variable Frequency Drives, etc.
September 19, 2025
Bug Fixes
- Available Transfer Capability (ATC) Tool: Custom expression and custom string expression fields for Branch Limiters and Interface Limiters in ATC results were not displayed correctly. This has been fixed.
- Case Information Displays: Unnecessary messages were being written to the log when using Quick Filters. This has been fixed.
- Oneline Diagrams: The Oneline Display Options dialog was not properly saving the integer option for "Maximum number of open onelines". This was properly being set and saved on the Simulation Options dialog, but not from the Oneline Display Options. It now works on both dialogs.
- Transient Stability: SVSMO3 and CSTCNT transient Switched shunts will now show the currents I Amps and I pu results. Before they were showing zero.
September 15, 2025
Features and Improvements
- Transient Stability: Changed the behavior for Load Relays in Transient Stability so that when they trip they take out fractional amount of both the Load Characteristics and the Load Distributed Generation models.
- Transient Stability: Fixed an access violation for transient when line shunts substations were nil.
Bug Fixes
September 11, 2025
Features and Improvements
- Transient Stability: Updates made to VHVDC2 to no longer freeze dynamic states and to use the measured voltage when calculating the Pmeas/Vmeas uses in the reactive capability curve lookup function.
- Auxiliary Files (SCRIPT and DATA Sections): Fixed Simulator option for DCModelType. The option should be GIgnore but it was previously looking for XIgnore which didn't make sense. This only impacted setting this option via an Auxiliary file.
Bug Fixes
September 9, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Added DCTransmissionLine to the objects available in the move script command, allowing users to move the dc transmission line.
- Transient Stability: In MSS1 and MSS2 switched shunt dynamic models, the thresholds for low and high voltage switching operations were correct in the data record but swapped in the dynamic model implementation. Users might have observed continuous repeated switching of the switched shunt in the events list, or seen a forced oscillation type of behavior in certain bus voltage magnitude or frequency signals. This has been fixed.
Bug Fixes
September 8, 2025
Features and Improvements
- Oneline Diagrams: On the dialog for Auto-Insert Buses on a oneline, added a new check box option to "Only Insert Buses that are a FixedNumBus".
- Optimal Power Flow (OPF): The OPF option "Distribute Change Among Equal Cost Generators" (added on June 25, 2025) is now renamed more aptly as "Balance Marginally Similar Controls". This option is useful in balancing control variables that have similar sensitivity vectors in the OPF or SCOPF tableau, and providing a dispatch where groups of controls (based on similar sensitivity) will participate in a manner that puts them in the same relative point within their linear cost segments. Without enabling this option, the behavior would be the as it was prior to June 25, which would incrementally assign control changes to one control at a time, until the desired impact is achieved by simplex linear program. The initial June 25 update provided a way to balance only Generator MW controls, and only under certain type of constraints. This present update handles all types of controls and all types of constraints that are present in the simplex tableau.
- Available Transfer Capability (ATC) Tool: The Reverse Buyer/Seller button on the ATC Dialog did not function properly if the existing Buyer and Seller were not the same type (for example both areas or both zones). This has been fixed so the types also are reversed.
- Case Information Displays: On the Contour Column dialog that Calculate Values button has been giving an error. It is now fixed.
Bug Fixes
August 26, 2025
Features and Improvements
- File Formats: When reading an hdbexport file containing CTGL records, modified so that if the B__CTGL is included with this record, then the object will only be read in if the B__CTGL <> 0.
- File Formats: Added support for reading/writing PSS/E RAW Version 36 files.
- General: Ability to see groupings of buses in common Phase Shift Groups - meaning that were all within the same grouping of 30 degree phase shifts in the network topology.
- General: Added a new object called a BranchGroupRating. A BranchGroupRating has a Name and a Description, and then all Branch objects can be assigned to belong to a BranchGroupRating. Then the BranchGroupRating has fields LimitMVAA..LimitMVAO which will show a value if all Branch objects in the BranchGroupRating have the same value. Otherwise these limits fields for a BranchGroupRating will show a blank. These Limit fields for a BranchGroupRating can then be edited to change the respective limit on all Branch objects assigned to the BranchGroupRating to the newly specified value.
- Optimal Power Flow (OPF): With the LP Basis Matrix added a field to show the constraint ID using key fields. This will change based on the case information display option that allows the selection of Key Fields when identifying objects in certain fields.
- Transient Stability: Removed the transient stability option to "MVA Base for Input/Display of Generator Values". Values are now always entered on the generator MVA Base and can no longer be edited on the system MVA base.
- Available Transfer Capability (ATC) Tool: Fixed access violation that could result when running ATC analysis using the (IL) then Full CTG Solution and using a Ramping Method for an injection group Seller of Econimic Merit Order or Merit Order Close.
- Case Information Displays: When using the Load CSV File from any case information display, an access violation could result if clicking the Cancel button instead of choosing a file to open. This has been fixed.
- Distributed Computation: When running script commands for contingency, ATC, QV, and transient stability analysis that allow the use of distributed computing an upfront check is now done to determine if any computers have been specified for use with distributed computing. If not an error results and analysis cannot continue until computers are specified. This error will also result if SimAuto has not been registered.
- Oneline Diagrams: Fixed access violation closing Oneline Marker form.
- Simulator Automation Server (SimAuto): When running multiple instances of SimAuto simultaneously, Windows could return an error message causing Simulator to fail. This was caused by a problem accessing the Windows Registry when multiple SimAutos were doing this simultaneously. We have added code to gracefully handle this and not crash Simulator.
Bug Fixes
August 23, 2025
Bug Fixes
- File Formats: EPC file syntax requires a single line of text that says "end" to complete the file. If this was missing an access violation would occur when reading the EPC file. This has been changes so that Simulator just stops reading the file gracefully if the end is missing.
- File Formats: An error was made in writing a custom monitor contingency violation regarding a three-winding transformer to the PWB file which could cause access violations when viewing contingency results contained in the PWB file. This fixes it so we are able to properly read the PWB that was created.
August 20, 2025
Features and Improvements
- Contingency Analysis Tool: Added "Use Primary CTG as Reference for Remedial and CTG Actions" option with CTG Combo Analysis. This option will set the system state following the solution of the primary contingency as the reference state for RAS and CTG actions when solving the secondary contingencies. Added "Use Primary CTG as Reference for Limit Monitoring" option with CTG Combo Analysis. This option will set the system state following the solution of the primary contingency as the reference state for determining base case loading and change violations when solving secondary contingencies and determining violations.
- Transient Stability: Added the CLOSE transient stability event for a Bus. This event will only close all of the branches connected to a bus.
- Transient Stability: Added ability for writing a GENQEC model to the DYR format
- Transient Stability: Added ability for reading and writing the GENQEJ model from and to the DYD and DYR formats
- Transient Stability: Added ability to read from a DYR file a USRMDL named GENQEJU and convert to the GENQEJ standard library model
- Transient Stability: Added ability for reading and writing the REEC_E model from and to the DYD and DYR formats. Model is named REECE in the DYR format.
- Transient Stability: Added ability for reading and writing the REGCB1 model from and to the DYR format.
- Optimal Power Flow (OPF): When loads do not have a benefit curve, they should be not dispatchable in the OPF. This bug has been corrected.
Bug Fixes
August 15, 2025
Features and Improvements
- Case Information Displays: Added support for pasting in transformer vector groups and showing the winding configurations for three-winding transformers.
- Integrated Topology Processing (ITP): Fixed access error when saving out a consolidated Case in Integrated Topology Processing if certain unique topologies existed around switched shunts.
- Integrated Topology Processing (ITP): When writing out a Consolidated Case in Integrated Topology Processing as a PWB file, it was possible for the PWB file to contain a Interface Element for branch that no longer existed in the consolidated case.This can happen if the Branch is shorted out by a set of other parallel switching devices. In this situation the PWB file would be corrupted because the element doesn't exist. Two fixes were made to handle this:
(1) We not longer write out such a branch to the Consolidate PWB file and a warning message is written to the log when saving the PWB
(2) When reading an existing PWB file that had been written this way we gracefully handle the non-existant branch and do not create the respective interface element.
Bug Fixes
August 14, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Added script command RegionLoadShapeFile to load regions directly from a shapefile.
- Auxiliary Files (SCRIPT and DATA Sections): Fixed bug merging buses. We were assuming the bus being merged was the from bus of a incident line to be moved. This wasn't always true, and could cause problems like disappearing 3-winding transformers.
- General: In the Connections Menu there is a new dialog called Find Phase Shift Groups. This shows the user all the case phase shift groups, and has an option to remove the groups.
- Transient Stability: This was a bug in the script command TSPlotSeriesAdd that was not applying the filter correctly. This bug was fixed and now the filter is applied correctly.
Bug Fixes
August 6, 2025
Bug Fixes
- Transient Stability: Fixed an Access Violation happening when loading the REPC_D transient model from a dyd file. The access violation was happening after loading the dyd file and then opening a different case or closing PowerWorld. This issue was fixed.
August 5, 2025
Features and Improvements
- Transient Stability: Added BASOEL2 over-excitation limiter
- Transient Stability: Fixed a bug regarding loading a transient stability switched shunt model from a dyd. When the ID in the dyd file was in a different case than the ID in the case it was not loading the transient model. For example the dyd file has the id on lowercase but the case has the ID in uppercase. This bug is now fixed.
Bug Fixes
July 29, 2025
Bug Fixes
- Optimal Power Flow (OPF): Corrections to the new option in OPF to "Distribute Change Among Equal Cost Generators", which was added on June 25, 2025. The method for grouping and redistribution of MW controls has been changed to ensure that all members of a group have the same relative MW setpoint along their respective current cost curve segments.
July 28, 2025
Features and Improvements
- Transient Stability: Added GENQEJ machine model
- User Interface Dialogs: Adjusted the font color of cells in tables that are object dialogs like piecewise linear cost curves for generators.
- Auxiliary Files (SCRIPT and DATA Sections): Fixed parsing of HOWMUCH parameter for Move script command. There was an error in parsing the HOWMUCH paramater when the AbortOnError parameter was used, causing it to use the default value of 100%. This has been fixed.
- Distributed Computation: Fixed an issue with distributed computer verification where computers that are unavailable remain marked as "Unknown".
Bug Fixes
July 21, 2025
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): The CloseWithBreakers script command was not working correctly if trying to connect a Bus object using breakers. This has been fixed.
- Contingency Analysis: When using OPENCBS actions with contingency analysis and no breakers can be found that isolate the element, an OPEN action on the element itself will be applied. This action is created as a dynamic action that should be cleaned up at the end of contingency analysis. This wasn't happening so extra messages might appear in the message log or What Occurred as subsequent contingency runs are done. This won't affect the contingency results. This has been fixed.
- Transient Stability: Added support for the transient model REGCBU1 to be able to read and write out from and to a dyr file. The model translate to REGC_B in PowerWorld.
July 15, 2025
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): Injection group contingency actions to ChangeBy or SetTo were not being implemented correctly using linear calculations with ATC when using the option to Linearize Makeup Power Calculation. This has been fixed.
- Transient Stability: Modified the CHVDC2 model to ensure enough subinterval integration timesteps are used for large Kir or Kii paramters for for very small time delays in the model.
- Transient Stability: When reading a CHVDC2 model from a DYR file, we now populate several fields in the extra DCLine model fields which are needed to properly write back out an EPC/DYD file pair that matches the system behavior.
- Transient Stability: The DYD file CHVDC2 record does not have several input parameters because these are stored in the EPC file DCLine and DC converter records. Because the DYR file stores this information, we must write that data into the appropriate location so we can write out an EPC/DYD file pair. This includes: DC line inductance, capacitance, converter smoothing inductance, DC margin at inverter, converter current rating, Max and Min alpha at the rectifier, and minimum alpha at the inverter.
July 14, 2025
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): When using the EditMultipleOnelineAction script command and choosing to save to a display auxiliary file, the file extension should be changed to AXD instead of leaving it as PWD. This has been fixed.
- General: There was a bug with the Create Composite Load Model tool which expanded a load model into load pieces along with the transformer and feeder. This issue is now fixed and the tool will split the composite load model into individual components without the bug.
- Transient Stability: Added the Generator Relay GENOOS. It is an Out of Step relay that will behave and be defined exactly as the Branch Relay OOSMHO Relay. The only difference is that the monitor flag meaning is as follows: Monitor. 0 = Alarm; 1 = Trip. The impedance is calculated at the terminal bus of the generator.
July 9, 2025
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): Reading devices from an AUX or Paste with multiple owners could fail to read correctly if the existing device and the Aux record for the device had some of the same owners but in different owner slots. Checking for duplicates was done after reading EACH owner from the Aux, which if true would remove the duplicate right away, rather than allow it during the AUX / Paste read so that owners could be sucessfully shifted to a different slot in the owner list. This has been modified so that removing duplicates is not processed while reading the Aux/Paste record, but rather waits until the end of reading the record to then check the list of multiple owners and remove any duplicates after all fields for the record have been read.
- Security Constrained OPF (SCOPF) Tool: Some marginal price values were being reported incorrectly after the completion of a SCOPF solution. This has been fixed.
- Transient Stability: The REPC_D model was causing a bug in transient stability if the system has an REPC_D model in the case that was causing an "Out of Memory" situation. This bug might also appear as an "Integer overflow" message. This bug was fixed and now the simulation will run without problems.
July 2, 2025
Features and Improvements
- Transient Stability: Added the ability to read 3 new commands for a transient contingency element when reading an OTGD file. The commands are for Bus Isolation (Open the bus), Branch Set R and X (Resistance and Reactance) and Opening shunts.
Examples:
1) "bus 'BUS 138'" "isol" 0.56667
2) "secdd 'BUS 500' '22222' '1' 1" "setto 0.0003 xpu" 0.50000
3) "svd 'BUS NAME 345' '99'" "open" 0.56667 - Auxiliary Files (SCRIPT and DATA Sections): Using the special string @CASENAME with script commands and plot features will include the full file path along with the name. Previously, this wasn't always true and depended on how a case was opened.
- Sensitivity Calculations: On the PTDF dialog the button to Visualize PTDFs is showing when the dialog is opened with the Multiple Directions option selected. This button should not be visible when calculating multiple directions. This has been fixed.
Bug Fixes
June 30, 2025
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): When loading an AUX file creating breakers/disconnects inside of a FixedNumBus grouping, the aux file was not permitting the branches to be created without unique IDs. This has been fixed as the IDs inside a FixedNumBus need only be unique between the terminal Bus objects as both terminal FixedNumBus groupings are the same.
June 27, 2025
Bug Fixes
- Oneline Diagrams: Fixed access violation that would result when opening the Oneline Viewer.
- Sensitivity Calculations: Interfaces that have contingency elements will now give the same results (MW and sensitivities) regardless of the order in which the contingency elements are defined in the interface.
- Sensitivity Calculations: It was possible for multiple element shift factor calculations to give different results for interfaces containing contingency elements when compared to the calculation for a single interface. This would happen if there was a least one interface included in the multiple element calculation that isolated generation or load. This has been fixed.
June 25, 2025
Features and Improvements
- Available Transfer Capability (ATC) Tool: Added new fields for a TransferLimiter object under the folder named Contingency Single Element. All of these field will be blank if there is no associated contingency or if the contingency has more than on ContingencyElement in it. If the associated contingency has only one contingency element, then it will show the field of that single ContingencyElement.
- Bus View and Substation View Onelines: Modified the Substation View so that it can use the exact same customizations as the Bus View. The substation view customization is much more limited though as it will only use the customizations for Branch Fields. The other fields (Bus, Gen, Load, Shunt) are all still visible on the dialog specifying the customization, but they are not used on the Subview. The customizations of Subview and Busview are share between the two views, so editing them in one location is also editing them in the other.
- Case Information Displays: Added two new fields to a Substation, Area, and Zone to show a space-delimited list of Nominal kVs in the substation. Useful to show on oneline diagrams and the substation view.
- Case Information Displays: Added ability to do column contouring on all matrix case information displays.
- Contingency Analysis Tool: Added new fields for a Contingency object under the folder named Single Element. All of these fields will be blank if the contingency has more than one ContingencyElement in it. If the contingency has only one contingency element, then it will show the field of that single ContingencyElement.
- General: Made improvements to ensure that the message log is not degrading software performance when the message log is not visible.
- Optimal Power Flow (OPF): Added a new option in OPF to "Distribute Change Among Equal Cost Generators". When a group of controls have an identical cost and also identical sensitivities on all binding constraints, then the OPF algorithm will now proportionally move the controls between the breakpoints of the cost curve instead of simply picking the generator with the minimum bus number first.
June 16, 2025
Bug Fixes
- Transient Stability: More modifications for how subinterval integration is handled for CHVDC2
June 12, 2025
Features and Improvements
- Case Information Displays: Modified a Region so that calculated fields of Bus, Gen, Load, Shunt, Branch, etc... will work on a Region
- Case Information Displays: Modified a Region so that it can be used as Device Filter on other object types and also use advanced filters of Regions on other objects.
- Case Information Displays: Modified Region objects so they can belong to ObjectGroups. This way a user can create an ObjectGroup of Regions and use this as a device filter to choose things.
- Oneline Diagrams: Modified oneline object linking to the existing case to accomodate FixedNumBus methods of identifying Gens, Loads, Shunts, Branches, DCLines and MSLine. This was generally supported already for creating new onelines, but when loading an old oneline made on a case that did not include the full topology it was not correctly linking when loading into a case which did contain the full topology.
- Power Flow Solution: The March 12 patch introduced a feature to find problems in RAW file solutions related to FixedNumBus groupings with a mixed status (some buses are connected and others are disconnected). PowerWorld will automatically close in branches to connect generator, load or shunt objects at dead buses that the RAW file solution showed injecting power into the system. This patch ensures that the initial voltage guess for these newly closed in buses is equal to the bus to which these buses are being connnected. Normally Simulator would do this automatically previously, but sometimes when opening the RAW file while in Edit Mode it was not.
- Transient Stability: When exporting transient stability data in the DYD file format, the "_cmpldw" composite load model associated with a PSLF load group (load zone, area, zone, owner) was missing the initial four parameters PMin, PQMin, VMin, kVThresh. This has now been corrected. This change does not impact the exporting of "cmpldw" composite load model associated with an individual PSLF loads that are identified by the bus number and id.
Bug Fixes
June 9, 2025
Features and Improvements
- Case Information Displays: Regions can now be combined on the Regions case info display by right-clicking and selecting Region Records, Combine Selected Regions
- GIC: Implemented the ability to read in the *.gic version 5 files even with full topology cases.
- General: Fixed an access violation that could occur whenever opening a new case or closing Simulator.
- Transient Stability: A recent patch was added to catch non-linear governor gains where either All GV or All PGV values are zero and default them to ignore the non-linear gain block. This was good to catch, but we were also catching as an error when all Gv AND Pgv are zero which has always mean to ignore the gain block. New check will properly ignore when both sets of values are zero and not report an error.
Bug Fixes
June 4, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Added new script command CalculateTapSense(filtername); The filtername can be empty meaning to do calculation for all transformers. Otherwise it can be a filter string for a Branch object using the same syntax as all other script commands.
- Case Information Displays: adding InjectionGroup fields for MWMaxA, MWMaxB, MWMaxC, MWMaxD, MWMinA, MWMinB, MWMinC, MWMinD and also MWMaxPercentA, etc. The Min/Max fields are enterable fields stored with the case. The Percentage fields show the percentage of the given limit. We expect the MWMax fields to be positive numbers and the MWMin to be negative numbers (for a load limit), but this is not enforced.
- Case Information Displays: Added ability to easily export TPWStringGrid results into shapefiles as long as they have geographic information. It is now available in the right-click menu, Geographic Data Views submenu; the two commands (Save Selected Objects in Shapefile or Save All Objects in ShapeFile) are at the end of the submenu. Data is exported as geographic points, with the exception that Regions are exported as polygons.
- Power Flow Solution: Added additional voltage preprocessing to the AC power flow solution to look for groups of buses connected by low impedance branches and then see if the buses within that group have very different per unit voltages. We can then choose a better initial voltage for this grouping which reduced the initial mismatch if available.
- Transient Stability: Added support to read and write the Bus model REPC_D to PSLF dyd format.
- Transient Stability: Added a new Transient Stability option to set how the relay will only scale/affect the load trips and the dist gen connected to a load. The options are to affect 1) Only Load MW and MVAR, or 2) Dist Gen and Load MW and MVAR. It is a new radio group in the Load Modeling Options. Currently the dist gen in the load were not affected by the load relay or scaling of the loads. That is now changed, and the new option will handle that.
- Transient Stability: fixed error in reading the ESST1C, ESST5C, ESST6C, and ESST7C models from a DYD file. We added the SCLFlag recently to support PowerWorld implementation of allowing a choice where the SCL input occurs. This parameter is not in the DYD file however so we need to handle this.
Bug Fixes
May 28, 2025
Features and Improvements
- General: Added a new button on the Case Information Ribbon for Cleanup Case Memory. This features provides a summary of how much of the PWB storage is being used to store different portions of the case data. In particular Transient Stability results and Geographic Regions can consume a large amount of memory. The dialog then provides convenient mechanisms to delete this information permanently
- Oneline Diagrams: The variable tap ratio is always on the From-Bus side, but on a oneline diagram it was difficult to tell which side that is. Modified the transformer symbol to provide a visual indication about which side of the transformer is the variable tap ratio on.
- Transient Stability: For the IEEEG1_GE and IEEE_G3_GE models, a negative db2 parameter has always been treated as a 0.0 deadband. A warning message has been added to alert the user this is happening.
- Oneline Diagrams: Fixed access violation that could occur when adding a new bus to a Bus Spatial View Oneline.
- Power Flow Solution: Eliminated some unnecessary recalculation of flows and sensitivities for interfaces that contain contingencies. These only need to be redone if there IS a change to system topology or elements in the interface and they were being redone if there MIGHT be a change to the elements within the interface.
- Sensitivity Calculations: The calculation of PTDFs and OTDFs for ATC analysis will now include the impact of losing a bus that is participating in the transfer because contingency actions isolate the bus. Previously only the impact of generator and load outages was included.
- Transient Stability: For non-linear gain look up tables in Governor models (for the gate position signal), additional checks have been added. Previously when all GV AND PGV values were 0.0, then the non-linear gain block was ignored and a fixed gain of 1.0 was used. Additional checking is now done so that if all GV values 0.0 then the non-linear gain block is also ignored. Also, if all PGV values are 0.0 then the non-linear gain block is ignored.
Bug Fixes
May 22, 2025
Bug Fixes
- Power Flow Solution: If you have a solve DC power flow solution, but one of the generator MWs is outside of its MWMin - MWMax limits, the DC power flow solution would not immediately enforce the generator limits. It required a mismatch in MW somewhere in the area to force this to be updated. This is now fixed so that the DC power flow solution will immediately enforce generator MW limits even on a solved DC power solution.
- Transient Stability: For the OEL2C model, the IfdRated input parameter is now used as a base to adjust Kscale automatically. When Kscale is specified as 1.0 and IfdRated <> 0, Kscale is internally calculated as 1/IfdRated. If a model specifies a value of Kscale that is not 1.0, then the Kscale value is retained as-is for the simulation. If a model truely needs a Kscale value of 1.0, then IfdRated must be specified as 0.0 or 1.0.
May 21, 2025
Bug Fixes
- Contingency Analysis: When using linear contingency methods and line outages end up isolating buses, the order of the contingency element definitions could cause slightly different results. This has been fixed.
- General: Fixed access violation error in Anonymize Names in Case.
- Power Flow Solution: Interfaces with open line contingency actions that cause generators, loads, and buses to be isolated will account for these changes in the interface MW flow, shift factors, and PTDFs. Previously only generators and loads that were explicitly modeled as outages in the interface would be handled.
- Security Constrained OPF (SCOPF) Tool: Modified to check the validity of running the SCOPF immediately when attempting to solve an SCOPF. Simulator has long had validity checks to ensuring that areas or superareas existing that were on OPF control and there were generator or load control available for AGC. However, there was not a check immediately to ensure AGC was enabled for the entire case and that Island-based AGC was not enabled. Instead, PowerWorld Simulator would run all the contingencies and then tell there user there was a problem. This has been fixed so the obvious validity checks are done immediately.
- Sensitivity Calculations: Interfaces with open line contingency actions that cause generators, loads, and buses to be isolated will account for these changes in the interface MW flow, shift factors, and PTDFs. Previously only generators and loads that were explicitly modeled as outages in the interface would be handled.
- Time Step Simulation: Bug fix for script command TIMESTEPSaveInputCSV in which the weather values in MPH were not being written.
May 9, 2025
Bug Fixes
- Simulator Automation Server (SimAuto): When using the SaveCase() SimAuto command in a tight loop that may call SaveCase() many times in a short period of time, it was possible for Windows I/O errors to occur. This has been fixed.
- Transient Stability: Fixed an access violation caused by having DC line GIC related objects when starting transient stability.
May 7, 2025
Bug Fixes
- File Formats: For some rare PWB files, an access violation would occur when reading in the transient stability options in the PWB file. Getting this patch will allow you to read the existing PWB file you are having trouble with. The PWB itself was fine, but the reading of it had a bug in rare situations.
- General: It was possible to create an ObjectGroup or Region that had a leading or trailing space in the name which would be unique as compared to not having the spaces. This was confusing and has been fixed.
- User Interface Dialogs: Fixed error on the Set Bus Field From Closest dialog. When choosing a filter for either "Area/Zone filters" or for "Selected" it was not working properly. This has been fixed.
May 5, 2025
Bug Fixes
- Power Flow Solution: Angle smoothing could result in bad voltages estimates if smoothing was attempted across buses that have just been connected. A check has been added to not do smoothing in this situation and only voltage estimates on newly connected buses will be done. This should result in much better voltage estimates.
May 2, 2025
Bug Fixes
- Transient Stability: Fixed a bug in transient stability islanded total value. if the case has an island that was not viable and there was a load with a composite load model, the islanded total value was initialized to a Nan value and was dispalying the incorrect value. This was not affecting the simulation in any way, just was showing the incorrect result. This issue has been fixed.
- User Interface Dialogs: The 'Total Injection Increase/Decrease' and 'Flow Achieved' text boxes on the 'Line Loading Replicator' were not being populated after calculating the injection changes. This has been fixed.
May 1, 2025
Features and Improvements
- Transient Stability: New stability model names REPCGFM_C1 plant controller which has control algorithm for regulating P, Q, V and Frequency
- Power Flow Solution: When interfaces contain line contingencies that cause buses to become islanded, numerical problems can be encountered with the linear solution used for determining the impact of the contingent elements on the other contingent elements within the interface. This can cause inconsistent results. This has been fixed.
Bug Fixes
April 29, 2025
Bug Fixes
- General: When choosing to "Export Object Fields" to either a text file or Excel when a power system case had not yet been opened, an access violation occurred. This has been fixed.
April 28, 2025
Features and Improvements
- Transient Stability: Added support for a new VSCDCLine model in stability named VHVDC2 which is very similar to VHVDC1
- File Formats: Two-Terminal DC line in PowerWorld Simulator have a field for allowing the user to specify the GE EPC file bus number for the DC terminals of the device. If these are populated with 0 values we should should be automatically choosing unused numbers. This automatic calculation was not working properly and is now fixed.
Bug Fixes
April 23, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): DoCTGAction script command will now handle OPENCBS and CLOSECBS actions the same way that contingency analysis implements these actions. Previously these actions were not implemented.
- Available Transfer Capability (ATC) Tool: Changed the name of the bus field ATCMinTransLimMW to instead be ATCMinTransLimMWSource (we will still read the old field ATCMinTransLimMW and map that to ATCMinTransLimMWSource).
- Available Transfer Capability (ATC) Tool: Added a new Bus Field named ATCMinTransLimMWSink which returns the minimum Trans Lim value of the ATC Transfer Limiters where this bus is the Sink of the transfer for a transfer direction studied with Multiple Directions ATC and only a single transfer direction has this bus as the Sink. This field matched the field ATCMinTransLimMWSource for the Source
- Oneline Diagrams: Modified the BusView and SubView so that the right-click options for "Open External Maps" will work by getting the latitude/longitude coordinates from the Bus or Substation. Previously those features were never available because the BusView and SubView were not geographic-based onelines.
- Transient Stability: Modified display of the list of PlayIn signals in the Plot Designer so they are sorted in numerical order of the PlayInInfo always. Previously we were sorting like a string so the order was 0, 1, 10, 11 instead of 0, 1, 2, 3 etc.
- Transient Stability: New stability model names REPCGFM_C1 plant controller for use with machine model REGFM_C1 which has control algorithm for regulating P, Q, V and Frequency
- Transient Stability: Added the Ierr signal under the "OEL Other" folder in the plots section for the OEL2C model.
- User Interface Dialogs: Region information is now shown on the geography page for the bus and substation run-time dialogs; region information is also available in the Case Information displays (geography section) for buses, generators, loads, switched shunts, substations, areas and zones.
- Auxiliary Files (SCRIPT and DATA Sections): There was an access violation caused by removing a user named state via script command via the DeleteState script command if the state did not exist. This has been fixed.
- Case Information Displays: The tool to Export Case Object Fields was only reporting fields that had not been translated. This has been fixed again and all fields will be reported now.
- Case Information Displays: Fixed bug calculating generation in an owner. It was including offline generators in the generation sum. A check on the generation status has been added to fix this.
- Time Step Simulation: fixed a time step simulation issue in which some of the input fields were being shown as blank when the inputs had not yet been processed.
- Transient Stability: The OELInput parameter for the OEL2C model in a PSSE DYR file, has acceptable values of 1 (psse default), 2, 3, which are now correctly translated to the values 1, 0, 3 respectively in PowerWorld Simulator. Earlier, this translation was not being done while reading and writing a DYR. Already saved PWB files will be affected, and users will need to reload a DYR file in order to correctly translate this parameter.
- Transient Stability: The SW1 parameter for the OEL2C model in a PSSE DYR file, has acceptable values of 1, 2, which are now correctly translated to the values 0, 1, respectively in PowerWorld Simulator. Earlier, this translation was not being done while reading and writing a DYR.
- Transient Stability: During initialization of OEL2C, if modification limits is allowed, and if OEL ramp rate logic, Z is greater than or equal to zero, then the Iinst upper limit will be modified to match Iact. This is done to ensure that Ierr is greater than or equal to zero, and VOEL initializes to the upper limit, which is consistent with the OEL being idle.
- Transient Stability: Added initial limit modification for VOELmax1 provided the OEL is being initialized as idle. VOELmax2 and VOELmax3 were already being considered, and had missed to do it for VOELmax1.
Bug Fixes
April 15, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Do not put any restrictions on AXD script commands for being allowed when a load of an AXD file is treated as a complete oneline. Loading as a complete oneline is assumed when using the LoadAXD script command and creating a new oneline at the same time. At this point there seems to be no reason to restrict when AXD script commands can be applied.
- Available Transfer Capability (ATC) Tool: When using the ATC tool to ramp a scenario to the transfer limit for the scenario, the ramping to this transfer limit might fail if there were any iterated limiters that ended up not being able to solve their contingency and fully find the iterated limiter. This has been fixed.
- Transient Stability: REPC_B model were showing the incorrect sign for fdbd2 and possibly fdbd1 and dbd.
Bug Fixes
April 14, 2025
Features and Improvements
- Transient Stability: Added new Hybrid Inverter-based renewable Machine model named REGFM_C1. This model is called a "hybrid" model because it acts as simultaneously a Grid Forming Converter and a Grid Following Converter. This model is in beta development in conjunction with the WECC Model Validation Subcommittee.
- Contingency Analysis: When writing out CON files with REMOVE SWSHUNT or ADD SWSHUNT commands, modified to ensure that the ID string is also written after the SWSHUNT command. We added ability to read these commands with or without the ID several months ago, but when writing we were still omitting the ID string.
- File Formats: When writing out MVA limits D..K for transformer windings to a RAW file we were mistakenly writing out limits D over and over. This has been fixed.
- Transient Stability: The feature for showing Stability Models with bold fonts to indicate non-default values was no longer working. This has been restored.
- Transient Stability: Fixed error which could cause the final point of a PlayInGen voltage/frequency value to be ignored.
- Transient Stability: There was a bug in REPC_C model where the dialog and columns were only showing the first 11 Switched Shunt objects being controlled by the REPC_C and were missing the 12th if it existed. Now this was fixed.
Bug Fixes
April 9, 2025
Features and Improvements
- Contingency Analysis Tool: Two fields were added for Custom Monitors in Contingency Analysis -- Min Value Ctg Name and Max Value Ctg Name, which show the name of the contingency corresponding to the Min Value Cont. and Max Value Cont. respectively.
- Contingency Analysis Tool: For contingency actions that perform InjectionGroup Set/Change MW values by opening generation or load, a single WhatOccurredDuringContingency entry for the InjectionGroup is created indicating how must generation or load has been tripped and the MW Effect if relevant. This patch adds additional WhatOccurredDuringContingency entries listing the specific generator and loads and how much each has changed the MW injection. This doesn't impact the solution, but adds additional useful reporting.
- Data Checks: Could get a "duplicates not allowed" error when trying to open the Data Check tool. This has been fixed.
- General: Regions: provided option to use a much faster way to save the boundary points in aux files. Improved the region form performance with larger boundary point sets.
- Transient Stability: Added a new transient option called "Allow Creation on Dialog of Faults which Calculate Effect Impedance from Sequence Networks (Not Recommended)". The use of this option is not recommended. When choosing it, you will be able to create fault actions that calculate the effective impedance from the sequence networks. We do not recommend this because most of our users running transient stability do not have sequence network information available and instead make use of features such as applying a given fault impedance or applying a fault to achieve a per unit voltage.
- Auxiliary Files (SCRIPT and DATA Sections): Fixed a bug in the code for reading three winding transformers from an Auxiliary file. We were getting an access violation when a three winding transformer was read that was considered new, but had a duplicate star bus listed as an existing three winding transformer. This requires us to create a new star bus and that was causing an access violation in Simulator. This is now fixed.
- Available Transfer Capability (ATC) Tool: When using one of the iterated ATC methods and the source and sink are injection groups, participation factors will remain constant throughout the analysis even if participation factors are set to be auto calculated. The assumption is they should only be auto-calculated once at the start of running the ATC.
- Data Checks: Could get a "duplicates not allowed" error when trying to open the Data Check tool. This has been fixed.
Bug Fixes
March 31, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Added a new script command DirectionsAutoInsertReference(SourceType, SinkObject, DeleteExisting, SourceFilterName, OppositeDirection);
SourceType : Bus, Area, Zone, or InjectionGroup
SinkObject: "Slack", or the objectname plus keyfield or label identifiers for a specific Bus, Area, Zone, or InjectionGroup
DeleteExisting: YES or NO
SourceFilterName: a string showing the name of a filter for which Source objects to use
OppositeDirection: YES or NO - Available Transfer Capability (ATC) Tool: Modified the Auto Insertion of Directions dialog to allow the user to specify if the Reference is the Sink or the Source. Previously the Reference was always the Sink. For doing studies of transferring power to large loads it is useful to do the opposite.
- Auxiliary Files (SCRIPT and DATA Sections): The tool to Export Case Object Fields was not properly working. This has been fixed and all fields will be reported now.
- Simulator Automation Server (SimAuto): Updated SimAuto's GetSystemMetrics to correctly report logical processor counts on machines with >64 cores
Bug Fixes
March 25, 2025
Bug Fixes
- Auxiliary Files (SCRIPT and DATA Sections): When loading Model Expressions from auxiliary files the expressions were not properly initialized. This resulted in this error reported with each expression: "ERROR: Expression object not created." This has been fixed.
March 24, 2025
Features and Improvements
- Oneline Diagrams: Added an option to allow the user to specify the amount of spacing between parallel lines on the auto line insertion.
- User Interface Dialogs: Added a few new fields to the Regions dialog; also added field to show the regions associated with a bus.
- Auxiliary Files (SCRIPT and DATA Sections): Fixed bug with loading 3WXformer objects from an Auxiliary file. Objects would not be found correctly.
- Available Transfer Capability (ATC) Tool: When using an iterated method with ATC analysis and the full transfer step is not able to be achieved in the part of the process where all limiters are iterated on to determine the order in which individual limiters will be iterated on, the remaining limiters that are not iterated on individually might have their Trans Lim values increased incorrectly by the amount of transfer that was able to be achieved in the last step of the initial process when the POWERFLOW DIVERGENCE limiter is recorded. This has been fixed.
Bug Fixes
March 21, 2025
Features and Improvements
- Case Information Displays: Added a new field CountTransformer (Number Of\Transformers ) for both a Bus, Zone, Area, and Substation object to show the number of Transformers attached to the Bus, or at buses inside the groupings.
- Case Information Displays: Added new fields for a Bus object named ZBRGenList, ZBRRegBusList, ZBRRegBusConflict, ZBRVoltSetList, and ZBRVoltSetConflict. These fields are then shown on a new case information display available in the Model Explorer under Solutions Details\Regulating Buses Multiple Local. The fields are populated with information when grouping of buses connected by low impedance branches have multiple generators connected to them. They will then show a list of bus number of regulated buses and a list of voltage setpoint voltages, and if there are multiples of these representing a conflict field will say YES. This can be helpful in debugging conflicting input data that is not as obvious as generators at the same bus having different regulation buses or setpoints.
- File Formats: Simulator Version 24 reads the RAW file field for a Branch and Transformer called NAME as an object label. For many years, PowerWorld has also seen RAW files in particular written out of EMS systems that included special syntax inside of Comment strings at the end of RAW file records. These comments included an object label inside of square brackets. This ad-hoc syntax had been used for years by customers to include labels. The original release of Simulator 24 read both of these locations as a label, but the NAME field was given priority and set as the Primary Label inside Simulator. Users however are finding that the values in the comment are more predictably set as labels, so we have changed it so the ad-hoc syntax in the comment string is set as the primary label instead.
- Oneline Diagrams: When reading a Shapefile (*.shp) into a oneline, Simulator will now look inside the PRJ file (if available) at the PROJECTION specified. If the PRJ file has a PROJECTION equal to "Mercator_Auxiliary_Sphere" then Simulator will automatically assume it map projection that is very commonly used for Shapefiles associated with website platforms such as Google Maps, Bing Maps, and so on. When this is detected now, Simulator will automatically convert the coordinates in the SHP files to Latitude/Longitude coordinates using this assumed map projection. In older versions of Simulator the user could click a button on the Modify Tab of the Shapefile import form, but this will now be done immediately upon loading the file.
- Oneline Diagrams: Fixed bug when loading a Shapefile (*shp) if a companion Projection file (*.prj) did not exist. The PRJ file should not be required when reading the SHP file, but an error would appear saying that the file could not be found.
Bug Fixes
March 18, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): The DetermineShortestPath script command was not correctly reading the parameter for BranchDistanceMeasure resulting in a returned error. This has been fixed.
- Contingency Analysis Tool: Fixed linear methods for calculating contingency actions for setting or changing an injection group in merit order. Actions using merit order open were correctly implemented.
- Contingency Analysis Tool: When using linear methods for calculating contingencies, the accounting of the gen or load dropped by injection group Set To and Change By actions used when reporting results was not correct. This has been fixed.
- File Formats: The features added over the last couple patch related to the problem in many RAW files where disconnected generators, loads, and shunt were still providing MW and Mvar to the system has been confirmed as a known problem in the RAW file solutions. This patch modified the dialog appearing telling the user about this problem so the dialog is informational only. PowerWorld will now always close in switching devices to replicate the MW/Mvar flows of the incorrect RAW file solution.
- GIC: Mostly minor changes, including 1) updating the GMD code to show support for TLP-007-4, 2) starting to add support for the new geomagnetic north pole locations, 3) support for viewing GIC files in the file browser, 4) adding an automatic upload of the region buses when they are loaded from an aux file.
- User Interface Dialogs: Added support for user interaction with the Message Log using the Mouse Wheel and keyboard UpArrow, DownArrow, PageUp and PageDown keys.
MouseWheel up and down will scroll the messages log without changing selection.
Ctrl+MouseWheel will zoom in and out (change font size).
Shift+MouseWheel will expand the selection up or down by one row.
Up/Down Arrow will move the selection up/down one row.
Shift+Up/DownArrow will expand the selection up/down one row.
Ctrl+Up/Down will zoom in and out (change font size).
PageUp/PageDown will move the selection up/down the number of visible rows.
Shift+PageUp/PageDown will expand the selection up/down the number of visible rows.
Ctrl+PageUp/PageDown will zoom in and out faster (change font size).
March 14, 2025
Features and Improvements
- Case Information Displays: When right-clicking on a case information display and choosing "Set all Values To", the dialog box that appears will now automatically have the edit box for entering a value focused so you can immediately start typing the number.
- Case Information Displays: Fixed various location where copy/pasting the Latitude and Longitude field into a table was not working.
- Case Information Displays: Generator, Load, and SwitchedShunt objects were not working when copy/pasting (or loading from a CSV) because it would say the key fields were missing, even though the ID field was there. This was NOT impacting auxiliary files, but was unique bug to copy/pasting (or loading from a CSV) which were based on column headings.
- File Formats: The March 12, 2025 patch of Simulator 24 had a bug that would impact the ability of the March 5, 7, and 10 patches ability to read the PWB file produced. The PWB file would still read find in the March 12 patch of Simulator 24, but not the previous patches of Version 24. This patch fixes it so PWB files created are read correctly by all Version 24 patches.
- Transient Stability: Eliminated a validation warning message for svsmo1,2 and3 about "The transient Xc parameter is different from the power flow Xc value". This message was created by mistake, even when the parameters were the same. If they are different values, that is handled in the initialization of the model and do not need a validation warning. The validation warning was removed from every situation.
Bug Fixes
March 12, 2025
Features and Improvements
- Auxiliary Files (SCRIPT and DATA Sections): Updated the Move script command to accept labels to specify the branch and also accept a bus label instead of a bus number for the destination
- File Formats: The Limit Monitoring option for "Do not monitor radial lines and buses" is no automatically reset to unchecked when loading a new RAW or EPC file. Previously it would remain at whatever setting it had before opening the RAW or EPC file.
- File Formats: In the previous patch, features were added when loading a RAW file that were locating incorrect treatment in RAW file solutions if FixedNumBus with a mixture of Connected and Disconnected substation node statuses. This patch introduces features to automatically determine switching devices that could be closed to match the incorrect RAW file solution and prompt the user asking them if they would like us to close these switching devices.
- Oneline Diagrams: Added Region Display Styles for creating automated oneline displays from geographic Region objects.
- Transient Stability: When a vertical axis is set to ScaleMinAuto and ScaleMaxAuto the axis extremes are calculated automatically, however PowerWorld has always internally ensured that the range at least shows a variation in the 5th significant digit. A new option has been added to allow the user to specify a ScaleAutoRangeMin. This will ensure that the auto extremes calculated are enforce that (AutoMax - AutoMin) >= ScaleAutoRangeMin. If the range is less than this then the new range will be set to the average of the AutoMax and AutoMin plus/minus the ScaleAutoRangeMin/2.
NewAutoMax = (AutoMax + AutoMin)/2 + ScaleAutoRangeMin/2
NewAutoMin = (AutoMax + AutoMin)/2 - ScaleAutoRangeMin/2 - Transient Stability: When ScaleMinAuto and ScaleMaxAuto are both set to YES and the user sets a value for ScaleInc, modified so that the maximum value used for an increment will be (Max-Min)/2 so at a minimum 3 points will be labels on the vertical axis. This prevents situations such as ScaleInc being set to 0.05 when the automatically determine Max is 1.02 and Min is 1.01 which would create a Y-axis without any scale because the increment was too big.
- Oneline Diagrams: The local menu when right-clicking on a branch display object on a oneline shows the From and To bus numbers listed at the top of the menu. The "To:" was not propertly showing the To bus but was instead just repeating the From bus. This has been fixed.
Bug Fixes
March 10, 2025
Features and Improvements
- File Formats: PowerWorld has found many RAW files with FixedNumBus groupings with a mixture of Nodes with Connected and Disconnected Status. At some of these nodes with Mixed Status, there are generator, load or shunt objects that meet the following criteria (1) Terminal is at a disconnected node, (2) device status = 1, and (3) MW or Mvar injection exists. Because the terminal nodes are disconnected for these devices by substation switching devices, they can not provide injection to the system. PowerWorld has found many RAW file solutions that have these disconnected devices supplying or absorbing power. Various messages log information is now displayed when this is encountered along with recommended switching devices that can be closed to replicated the RAW file solution.
- Transient Stability: Implemented a new UEL2CPTI model, that is created when reading in the UEL2C model record in a PTI DYR file. This new model has extra model parameters compared to a UEL2C model GE DYD file -- (i) an extra 11th pair (P10, Q10) in the lookup table, (ii) an extra limit pair (VULmax/min) on the VUEL output signal, and (iii) an extra parameter (Quad) that allows the lookup table to be used as mirrored around the MVAR axis when MW values are negative. This extra parameters are read/written from the text formats, and the are fully implemented during the dynamic simulation.
March 7, 2025
Features and Improvements
- Bus View and Substation View Onelines: Added a new visualization for Bus View to show "Consolidate FixedNumBus Splits" which will generally show FixedNumBus groupings but will automatically split up those groupings if there are multiple Superbus within the group. This ensures that the user can always see open breakers that have split the FixedNumBus
- Bus View and Substation View Onelines: Modified the "Consolidated Superbus" BusView to highlight other SuperBus which would be part of the Superbus if switching devices were closed or other things preventing consolidation were ignored.
- Bus View and Substation View Onelines: Modified the "Consolidated FixedNumBus" BusView to visualize the splits created by the open switching devices.
- Case Information Displays: A new field was added to a Bus, Gen, Load, and Shunt object called Solution\Status FixedNumBus. Shows either Disconnected, Connected, Mixed, Connected2, Mixed2, and so on. If all buses in the FixedNumBus are Disconnected it will show Disconnected. If all are Connected, then it will show Connected followed by the number of unique SuperBus that are inside the FixedNum Bus if more than 2. If there is are both Connected and Disconnected buses, then it will say Mixed.
- File Formats: When loading in other file formats, PowerWorld would set a bus' voltage could be set equal to another bus if it was radial to the other bus and also had no load, generation, or shunts. This improved solution convergence is cases written in other file formats. A message log is now written indicating this is happening.
- Transient Stability: Added support to read and write to a dyd file for the transient models OEL4C and OEL5C.
- Transient Stability: On generator dialog when adding a model the dialog which appears had the "folder icon" and the "blue dot icon" flipped. This has been fixed
- Transient Stability: Access violation bug when using certain system or groups transient model (like system wide WSCC load model) and opening a table of the transient models in the Model Explorer. Now the access violation will not occur.
- User Interface Dialogs: Changes were made to the look and feel of the selected text in the Message Log in Simulator 24. These changes caused the font size of the message log to be ignored and unchangeable. This has been fixed.
