Switched Shunt Model: CSSCST

Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < T3 < Mult*TimeStep then T3 = Mult*TimeStep
- If 0.0 < T4 < 0.5*Mult*TimeStep then T4 = 0, ElseIf 0.5*Mult*TimeStep < T4 < Mult*TimeStep then T4 = Mult*TimeStep
- If 0.0 < T5 < 0.5*Mult*TimeStep then T5 = 0, ElseIf 0.5*Mult*TimeStep < T5 < Mult*TimeStep then T5 = Mult*TimeStep
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Thyristor > MaxShuntB, then MaxShuntB= Thyristor or if Thyristor < MinShuntB, then MinShuntB= Thyristor
- Originaly, MaxShuntB = SwitchedShuntMaxShuntB and MinShuntB = SwitchedShuntMinShuntB
Model Equations and/or Block Diagrams
See CSVGN1, CSVGN3 and CSVGN4 for more information.
Parameters:
K | Gain |
T1 | Time constant 1 (sec) |
T2 | Time constant 2 (sec) |
T3 | Time constant 3 (<0) (sec) |
T4 | Time constant 4 (sec) |
T5 | Time constant 5 (sec) |
VMax | VMax (Mvars) |
VMin | VMin (Mvars) |
Vov | Vov (override voltage) (pu) |