Stabilizer Model: PSS6C
Following checks and corrections are applied during Validation and AutoCorrection.
-
If Ks <= 0 then Ks = Mult*TimeStep
- If K0 <= 0 then K0 = Mult*TimeStep
- If Vstmax < Vstmin then swap the values. If Vstmax < 0 then Vstmax change sign to positive. If Vstmin > 0 then change sign to negative.
- If Vsi1max < Vsi1min then swap the values. If Vsi1max < 0 then Vsi1max change sign to positive. If Vsi1min > 0 then change sign to negative.
- If Vsi2max < Vsi2min then swap the values. If Vsi2max < 0 then Vsi2max change sign to positive. If Vsi2min > 0 then change sign to negative.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vpss > Vstmax, then Vstmax = Vpss limits or if Vpss < Vstmin , then Vstmin = Vpss
Model Equations and/or Block Diagrams
Parameters:
| Ics1 | First stabilizer input code; 1=Rotor speed deviation (pu); 2=Bus Freq Deviation (pu); 3=Gen Pelec on Machine Base (pu); 4=Gen accelerating power (pu); 5=Bus voltage (pu); 6=Derivative of Bus voltage (pu); 7=Compensated Frequency Signal (pu) |
| Ics2 | Second stabilizer input code; 1=Rotor speed deviation (pu); 2=Bus Freq Deviation (pu); 3=Gen Pelec on Machine Base (pu); 4=Gen accelerating power (pu); 5=Bus voltage (pu); 6=Derivative of Bus voltage (pu) |
| Ks1 | PSS gain for input channel 1 |
| T1 | PSS transducer time constant for input channel 1 |
| T3 | PSS time constant for input channel 1 |
| Ks2 | PSS gain for input channel 2 |
| Macc | PSS washout time constant for input channel 2 |
| T2 | PSS transducer time constant for input channel 2 |
| T4 | PSS time constant for input channel 2 |
| Td | PSS washout time constant |
| K0 | PSS canoniocal gain 0 |
| K1 | PSS canoniocal gain 1 |
| K2 | PSS canoniocal gain 2 |
| K3 | PSS canoniocal gain 3 |
| K4 | PSS canoniocal gain 4 |
| Ki3 | PSS third block gain |
| Ki4 | PSS fourth block gain |
| Ks | PSS main gain |
| Ti1 | PSS time constant in first block |
| Ti2 | PSS time constant in second block |
| Ti3 | PSS time constant in third block |
| Ti4 | PSS time constant in fourth block |
| Vsi1max | Input Signal 1 maximum limit |
| Vsi1min | Input Signal 1 minimum limit |
| Vsi2max | Input Signal 2 maximum limit |
| Vsi2min | Input Signal 2 minimum limit |
| VSTmax | Maximum PSS output |
| VSTmin | Minimum PSS output |
| PSSActivation | Generator MW threshold for PSS activation |
| PSSDeactivation | Generator MW threshold for PSS da-activation |
| Tpgfilt | Filter time constant for Pgen used in PSS output logic |
| Xcomp | Reactance for compensated frequency calculation |
| Tcomp | Time constant for compensated frequency calculation |