Stabilizer Model: PSS4B
Following checks and corrections are applied during Validation and AutoCorrection.
- If TH <= 0 then TH = Mult*TimeStep
- If A <= 0 then A = Mult*TimeStep
- If KL1 <= 0 then KL1 = Mult*TimeStep
- If KL2 <= 0 then KL2 = Mult*TimeStep
-
If KI1 <= 0 then KI1 = Mult*TimeStep
- If KI2 <= 0 then KI2 = Mult*TimeStep
-
If KH1 <= 0 then KH1 = Mult*TimeStep
- If KH2 <= 0 then KH2 = Mult*TimeStep
- If Vstmax < Vstmin then swap the values. If Vstmax < 0 then Vstmax change sign to positive. If Vstmin > 0 then change sign to negative.
- If VLmax < VLmin then swap the values. If VLmax < 0 then VLmax change sign to positive. If VLmin > 0 then change sign to negative.
- If VImax < VImin then swap the values. If VImax < 0 then VImax change sign to positive. If VImin > 0 then change sign to negative.
- If VHmax < VHmin then swap the values. If VHmax < 0 then VHmax change sign to positive. If VHmin > 0 then change sign to negative.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| CLI | Filter parameter |
| DLI | Filter parameter |
| ALI | Filter parameter |
| BLI | Filter parameter |
| BWLI1 | Notch filter parameter |
| WLI1 | Notch filter parameter |
| BWLI2 | Notch filter parameter |
| WLI2 | Notch filter parameter |
| TH | Notch filter parameter |
| AH | Notch filter parameter |
| BH | Notch filter parameter |
| M | Ramp tracking filter |
| BWH1 | Notch filter parameter |
| WH1 | Notch filter parameter |
| BWH2 | Notch filter parameter |
| WH2 | Notch filter parameter |
| KL1 | Low band differential filter gain (p.u.) |
| KL11 | Low band first lead-lag block coefficient (p.u.) |
| TL1 | Low band numerator time constant (sec.) |
| TL2 | Low band denominator time constant (sec.) |
| TL3 | Low band numerator time constant (sec.) |
| TL4 | Low band denominator time constant (sec.) |
| TL5 | Low band numerator time constant (sec.) |
| TL6 | Low band denominator time constant (sec.) |
| KL2 | Low band differential filter gain (p.u.) |
| KL17 | Low band first lead-lag block coefficient (p.u.) |
| TL7 | Low band numerator time constant (sec.) |
| TL8 | Low band denominator time constant (sec.) |
| TL9 | Low band numerator time constant (sec.) |
| TL10 | Low band denominator time constant (sec.) |
| TL11 | Low band numerator time constant (sec.) |
| TL12 | Low band denominator time constant (sec.) |
| KL | Low band gain (p.u.) |
| VLmax | Low band upper limit |
| VLmin | Low band lower limit |
| KI1 | Intermediate band differential filter gain (p.u.) |
| KI11 | Intermediate band first lead-lag block coefficient (p.u.) |
| TI1 | Intermediate band numerator time constant (sec.) |
| TI2 | Intermediate band denominator time constant (sec.) |
| TI3 | Intermediate band numerator time constant (sec.) |
| TI4 | Intermediate band denominator time constant (sec.) |
| TI5 | Intermediate band numerator time constant (sec.) |
| TI6 | Intermediate band denominator time constant (sec.) |
| KI2 | Intermediate band differential filter gain (p.u.) |
| KI17 | Intermediate band first lead-lag block coefficient (p.u.) |
| TI7 | Intermediate band numerator time constant (sec.) |
| TI8 | Intermediate band denominator time constant (sec.) |
| TI9 | Intermediate band numerator time constant (sec.) |
| TI10 | Intermediate band denominator time constant (sec.) |
| TI11 | Intermediate band numerator time constant (sec.) |
| TI12 | Intermediate band denominator time constant (sec.) |
| KI | Intermediate band gain (p.u.) |
| VImax | Intermediate band upper limit |
| VImin | Intermediate band lower limit |
| KH1 | High band differential filter gain (p.u.) |
| KH11 | High band first lead-lag block coefficient (p.u.) |
| TH1 | High band numerator time constant (sec.) |
| TH2 | High band denominator time constant (sec.) |
| TH3 | High band numerator time constant (sec.) |
| TH4 | High band denominator time constant (sec.) |
| TH5 | High band numerator time constant (sec.) |
| TH6 | High band denominator time constant (sec.) |
| KH2 | High band differential filter gain (p.u.) |
| KH17 | High band first lead-lag block coefficient (p.u.) |
| TH7 | High band numerator time constant (sec.) |
| TH8 | High band denominator time constant (sec.) |
| TH9 | High band numerator time constant (sec.) |
| TH10 | High band denominator time constant (sec.) |
| TH11 | High band numerator time constant (sec.) |
| TH12 | High band denominator time constant (sec.) |
| KH | High band limit |
| VHmax | High band upper limit |
| VHmin | High band lower limit |
| VSTmax | Output limit, maximum |
| VSTmin | Output limit, minimum |