Stabilizer Model: IVOST

Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < T2 < 0.5*Mult*TimeStep then T2 = 0, ElseIf 0.5*Mult*TimeStep < T2 < Mult*TimeStep then T2 = Mult*TimeStep
- If 0.0 < T4 < 0.5*Mult*TimeStep then T4 = 0, ElseIf 0.5*Mult*TimeStep < T4 < Mult*TimeStep then T4 = Mult*TimeStep
- If 0.0 < T6 < 0.5*Mult*TimeStep then T6 = 0, ElseIf 0.5*Mult*TimeStep < T6 < Mult*TimeStep then T6 = Mult*TimeStep
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
K1 | Gain 1 |
A1 | Notch filter parameters |
A2 | Notch filter parameters |
T1 | Lead/lag time constant, sec |
T2 | Lead/lag time constant, sec |
VMax1 | Maximum 1 |
VMin1 | Minimum 1 |
K3 | Gain 3 |
A3 | Notch filter parameters |
A4 | Notch filter parameters |
T3 | Lead/lag time constant, sec |
T4 | Lead/lag time constant, sec |
VMax3 | Maximum 3 |
VMin3 | Minimum 3 |
K5 | Gain 5 |
A5 | Notch filter parameters |
A6 | Notch filter parameters |
T5 | Wahsout numerator time constant, sec |
T6 | Washout denominator time constant, sec |
VMax5 | Maximum 5 |
VMin5 | Minimum 5 |