Pref Controller Model: WTGWGO_A

Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tfltr < 0.5*Mult*TimeStep then Tfltr = 0.0
ElseIf 0.55*Mult*TimeStep < Tfltr < Mult*TimeStep then Tfltr = Mult*TimeStep
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
Vwgo | Voltage threshold below with the WGO function is initiated [pu] |
Pwgo1 | Power reference held during a fault when WGO is initiated [pu] |
rpw1 | Ramp rate at which power is increased from Pwgo1 to Pwgo2 [pu/s] |
Pwgo2 | Power reference held for Thold seconds after the fault [pu] |
rpw2 | Ramp rate at which power is increased from Pwgo2 back to normal [pu/s] |
Thold | Time for which the power reference is held at Pwgo2 [s] |
eps | Small hysteresis on voltage recovery to start the first ramp [pu] |
Tfltr | Voltage filter time constant [s] |