Machine Model: REGC_C

 

Model Equations and/or Block Diagrams

Parameters:

Tfltr Voltage sensor time constant
Te Generator network impedance time constant, seconds
rrpwr LVPL ramprate limit, p.u.
Re Generator effective resistance, p.u.
Xe Generator effective reactive, p.u.
Iqrmax Reactive current recovery positive rate limit (set to zero or negative value to disable)
Iqrmin Reactive current recovery negative rate limit (set to zero or positive value to disable)
Rateflag RateFlag; 0 means active current ramp rate, otherwise active power ramp rate
Imax Maximum curring rating of the converter, p.u.
DQFlag PQ priority Flag; 0 = Q priority, otherwise P priority
Kip Proportional-gain of the inner-current control loop [pu/pu]
Kii Integral-gain of the inner-current control loop [pu/pu.s-1]
Kppll Proportional-gain of the PLL [rad.s-1/pu]
Kipll Integral-gain of the PLL [rad.s-1/pu.s-1]
wmax Upper limit on the PLL [rad.s-1]
wmin Lower limit on the PLL [rad.s-1]
Vdip Vdip [pu], Voltage below which PLL integrator state is frozen