Governor Model: WNDTRB
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Ta < 0.5*Mult*TimeStep then Ta = 0, ElseIf 0.5*Mult*TimeStep < Ta < Mult*TimeStep then Ta = Mult*TimeStep
 - If 0.0 < T2 < 0.5*Mult*TimeStep then T2 = 0, ElseIf 0.5*Mult*TimeStep < T2 < Mult*TimeStep then T2 = Mult*TimeStep
 
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
                       
Parameters:
| Trate | Turbine rating, MW | 
| Ta | Actuator time constant, sec | 
| Kp | Speed regulator gain | 
| T1 | Speed regulator TGR numerator time constant, sec | 
| T2 | Speed regulator TGR denominator time constant, sec | 
| BPRmx | Blade pitch maximum rate, deg/sec | 
| Pwo | Initial wind power, pu |