Governor Model: UCBGT

 

Model Equations and/or Block Diagrams

   

Parameters:

Rp Electrical power feedback droop
Tp Electrical power feedback time constant
Rv Governor feedback droop
Kmwp Proportional gain for outer loop MW control
Kmwi Integral gain for outer loop MW control
rfmax Maximum limit on outer loop MW control loop
rfmin Minimum limit on outer loop MW control loop
Dbd Intentional deadband
Err Intentional error limit
Ta Acceleration control differentiator time constant
aset Acceleration limit set-point
Kpg Speed governor proportional gain
Kig Speed governor integral gain
Kdg Speed governor derivative gain
Tdg Speed governor derivative time constant
Kpa Acceleration control proportional gain
Kia Acceleration control integral gain
Kpt Temperature control proportional gain
Kit Temperature control integral gain
Fmax Maximum fuel flow command
FMin Minimum fuel flow command
Tlimit Temperature limit (in pu corresponds to fuel flow required for 1 pu turbine power i.e. = 1/Kt + Wfo) (4)
Tthcp Thermocouple time constant
Tn Heat transfer lead time constant
Td Heat transfer lag time constant
Tv Fuel system time constant
Vmax Maximum valve opening
Vmin Minimum valve opening
Fm Fuel flow multiplier; typically set to 1.0. In some cases this is equal to speed (e.g. liquid fuel system with shaft driven fuel pump)
Wfo Full-speed no-load fuel flow
Kt Turbine gain
Ttn1 Turbine transfer function numerator time constant 1
Ttn2 Turbine transfer function numerator time constant 2
Ttd1 Turbine transfer function denominator time constant 1
Ttd2 Turbine transfer function denominator time constant 2
x1 Turbine characteristic curve speed 1
Fx1 Turbine characteristic curve output for speed 1
x2 Turbine characteristic curve speed 2
Fx2 Turbine characteristic curve output for speed 2
x3 Turbine characteristic curve speed 3
Fx3 Turbine characteristic curve output for speed 3
Trate Turbine rating in MW