Governor Model: TGOV1 and TGOV1D

Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < T1 < 0.25*Mult*TimeStep then T1 = 0.0
ElseIf 0.25*Mult*TimeStep < T1 < 0.5*Mult*TimeStep then T1 = 0.5*Mult*TimeStep - If 0.0 < T3 < 0.25*Mult*TimeStep then < = 0.0
ElseIf 0.25*Mult*TimeStep < T3 < 0.5*Mult*TimeStep then T3 = 0.5*Mult*TimeStep - If Vmax < Vmin then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Valve > Vmax , then Vmax = Valve or if Valve < Vmin , then Vmin = Valve
Model Equations and/or Block Diagrams
Parameters for TGOV1:
Trate | Turbine rating, MW |
R | Permanent droop, pu |
T1 | Steam bowl time constant, sec |
Vmax | Maximum valve position limit |
Vmin | Minimum valve position limit |
T2 | Numerator time constant of T2, T3 block, sec |
T3 | Reheater time constant, sec |
Dt | Turbine damping coefficient, pu |
Parameters for TGOV1D:
R | Permanent droop, pu |
T1 | Steam bowl time constant, sec |
Vmax | Maximum valve position limit |
Vmin | Minimum valve position limit |
T2 | Numerator time constant of T2, T3 block, sec |
T3 | Reheater time constant, sec |
Dt | Turbine damping coefficient, pu |
dbH | Deadband High (pu) |
dbL | Deadband Low (pu) |
Trate | Turbine rating, MW |