Governor Model: H6E

 

Model Equations and/or Block Diagrams

Parameters:

trate Turbine power base, MW
fd

Flag for proportional elec power signal; 0 = Speed control mode - droop is based on gate servo stroke;

1 = Load control mode - droop is based on electric power

re Permanent droop for electrical power feedback, pu
rg Permanent droop for gate position feedback, pu
tpe Electric power feedback transducer time const, sec
tsp Shaft speed transducer time const, sec
kp Governor proportional gain
ki Governor integral gain
kd Governor derivative gain
td Derivative gain filter time constant, sec
velm Maximum gate actuator velocity, pu/sec
gmax Maximum gate actuator stroke, pu
gmin Minimum gate actuator stroke, pu
buf Upper limit of gate buffer region, pu
buv Max gate closing rate in buffer region, pu
kg Pilot servovalve gain
tg Pilot servovalve time constant, sec
blg Backlash in ring linkage
dbbd Deliberate sliding deadband in digital blade cam output
tbd Time constant of sliding deliberate dead band, sec
blb Backlash in blade adjustment linkage
dbbs Mechanical deadband in blade servovalve/motor
tbs Blade servo time constant, sec
bgvmin Flow area factor of blades when at minimum position
blv Maximum stroking rate of blade servomotor
dturb Turbine speed sensitivity constant
pgc Electric motoring power with gates fully closed, pu
deff Off blade angle power decrease factor
hdam Operating head, pu
tw water inertia time constant, sec
sprate speed-load setpoint adjustment rate, pu/sec
gv0 Abscissa value 0 for wicket gate and blade curves
gv1 Abscissa value 1 for wicket gate and blade curves
gv2 Abscissa value 2 for wicket gate and blade curves
gv3 Abscissa value 3 for wicket gate and blade curves
gv4 Abscissa value 4 for wicket gate and blade curves
gv5 Abscissa value 5 for wicket gate and blade curves
gv6 Abscissa value 6 for wicket gate and blade curves
gv7 Abscissa value 7 for wicket gate and blade curves
gv8 Abscissa value 8 for wicket gate and blade curves
gv9 Abscissa value 9 for wicket gate and blade curves
pgv0 Value 0 for Curve of wicket gate flow area
pgv1 Value 1 for Curve of wicket gate flow area
pgv2 Value 2 for Curve of wicket gate flow area
pgv3 Value 3 for Curve of wicket gate flow area
pgv4 Value 4 for Curve of wicket gate flow area
pgv5 Value 5 for Curve of wicket gate flow area
pgv6 Value 6 for Curve of wicket gate flow area
pgv7 Value 7 for Curve of wicket gate flow area
pgv8 Value 8 for Curve of wicket gate flow area
pgv9 Value 9 for Curve of wicket gate flow area
bgv0 Value 0 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv1 Value 1 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv2 Value 2 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv3 Value 3 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv4 Value 4 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv5 Value 5 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv6 Value 6 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv7 Value 7 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv8 Value 8 for Curve of Kaplan turbine blade flow area as function of gate servo stroke
bgv9 Value 9 for Curve of Kaplan turbine blade flow area as function of gate servo stroke

 

PowerWorld Implementation in Pseudo-Code

User Input Parameters for Model

ffd, ftrate, fre, frg, finvtpe, finvtsp, fkp, fki, fkd,

finvtd, fvelm, fgmax, fgmin, fbuf, fbuv, fkg, finvtg,

fblg, fdbbd, finvtbd, fblb, fdbbs, finvtbs, fbgvmin,

fblv, fdturb, fpgc, fdeff, fhdam, finvtw, fsprate : single;

// Note various parameters such as finvtpe are storing 1/tpe

fBackLash_blb, fBackLash_blg : BackLash Object; // see below

fP_Q, fB_GV : Nonlinear Lookup Tables

These tables are created from the input parameters GV0…GV9, PGV0…PGV9, and BGV0…BGV9.

See section below for details of how these are calculated.

 

Cached Values with model

These variables are availabe inside all functions.

cache_Spref, cache_LastTimeStepGateCommand, cache_GateCommand, cache_Hscroll,

cache_BC, cache_GV, cache_BB, cache_BH, cache_AB, cache_AF : double;

 

State and Derivative Value Syntax

Derivative[INDEX] : Derivative of state INDEX for model

StateVector[INDEX] : Value of state INDEX for model

IgnoreStateVector[INDEX] : boolean indicating if state INDEX is ignored

 

Nonlinear Lookup Curves (GV0…GV9, PGV0…PGV9, BGV0…BGV9)

After reading these input parameters three lookup tables are created

  // force fbgvmin to between 0 and 1, but not equal to those numbers

  if      fbgvmin < 0.00001 then fbgvmin := 0.00001

  else if fbgvmin > 0.99999 then fbgvmin := 0.99999;

  for i := 0 to 9 do begin

    // Calculate steady state Q for particular gate value

   QGV[i] := GV[i]*( fbgvmin + (1-fbgvmin) * BGV[i]);

  End;

  // Create lookup function and add first point. 

  // The FALSE in constructor means to not extrapolite past the start and end point

  fP_Q := PiecewiseLinearFunctionObject.Create(QGV[0],PGV[0],FALSE);

  fB_GV := PiecewiseLinearFunctionObject.Create( GV[0],BGV[0],FALSE);

  For i := 1 to 9 Do Begin

    if (GV[i] > 0) then begin

      fP_Q.AddPointInOrder(QGV[i],PGV[i]); // Power vs Q

      fB_GV.AddPointInOrder(GV[i],BGV[i]); // B vs Gate

    end;

  End;

// PiecewiseLinearFunctionObject just encapsulates a lookup function. 

// Method X(index) returns the X value of the X,Y part at a particular index

// Method Y(index) returns the Y value of the X,Y part at a particular index

// Method XtoY takes an input X value and calculates the output Y// Method YtoX takes an output Y value and calculates the input X

 

BackLash Object

    fDeadband : Double; 

    fLastOutput: Double;  // Tells the last output value

  Public

    Constructor CreateBackLash(tDeadband,tInitialOutput : Double);

    Function Output(anInput : Double) : Double;

 

BackLash.CreateBackLash(tDeadband,tInitialOutput : Double);

Begin

  fDeadBand := tDeadBand;

  If fDeadband < 0 Then fDeadband := 0;  // Must be non-negative

  fLastOutput := tInitialOutput;

End;

 

Function BackLash.Output(anInput : Double) : Double;

Begin

  If (anInput >= fLastOutput-fDeadband) and (anInput <= fLastOutput+fDeadBand) Then begin

   Result := fLastOutput;

  End

  Else Begin

    If anInput > fLastOutput+fDeadband

    Then Result := anInput-fDeadBand // Going up, subtract off deadband

    Else Result := anInput+fDeadBand; // Going down, add deadband

    fLastOutput := Result;

  End;

End;

 

Start of Each TimeStep

Begin

  cache_LastTimeStepGateCommand := cache_GateCommand;

 

  // Update the cache_Spref value using a rate limiter

  if Pref > cache_Spref then begin

    cache_spref := cache_spref + fsprate * timeStepSeconds;

    if cache_spref > Pref then cache_spref := Pref;

  end

  else if Pref < cache_Spref then begin

    cache_spref := cache_spref - fsprate * timeStepSeconds;

    if cache_spref < Pref then cache_spref := Pref;

  end;

end;

 

function to return the Pmech to feed to machine model

var local_Q, local_MinQ : double;

begin

  local_Q := StateVector[9];

  // hydraulic power

  if fP_Q.Count > 0 then begin

    local_MinQ := fP_Q.X(1);

    if (local_Q < local_MinQ) and (local_MinQ > 0)

    then result := cache_Hscroll * (fpgc * (local_Q - local_MinQ)/local_MinQ)

    else result := cache_Hscroll * (fP_Q.XtoY( local_Q ) - fdeff*sqr(cache_bh - cache_bb));

  end

  else begin

    result := cache_Hscroll * (local_Q - fdeff*sqr(cache_bh - cache_bb));

  end;

  result := result - deltaWPU * fDTurb * cache_GV;

  // put turbine power on appropriate per unit base

  result := result/GenObject.MVABase*fTrate;

end;

 

InitializeForIntegration Function

Var local_pq,

    local_gv,

    local_q,

    local_af    : Double;  // local values for initialization

    Local_Pmech : double;

    Local_PElec : double;

Begin

  Local_Pmech := GenObject.PMechObjectInitInternal;

  Local_Pmech := Local_Pmech*GenObject.MVABase/fTrate;

  Local_PElec := PElec;

  Local_PElec := Local_PElec*GenObject.MVABase/fTrate;

 

  local_pq := Local_Pmech/(1.0*fHdam);

  if local_pq > fP_Q.LastY then begin // added initial limit violation check in February 2022

    fHdam := local_Pmech / fP_Q.LastY; // added some log messages

    local_pq := Local_Pmech/(1.0*fHdam);

  end;

  local_q := fP_Q.YtoX(local_pq);

  local_af := local_q/sqrt(fHdam); 

 

  local_afmax := fgmax* (fbgvmin + (1-fbgvmin)*fB_GV.XtoY(fgmax) );

if (local_af > local_afmax)

     and LOCAL_BackSolveForQ(local_afmax, local_Pmech, local_q)

then begin // added initial limit violation check in September 2022

    local_gv := fgmax;

    local_af := local_afmax;

    fHdam := sqr(local_q/local_afmax); // added some log messages   

  end

  else begin

    local_gv := LOCAL_BackSolveForGate(local_af); // see on following pages

  end;

  // Modified fgmin and fgmax if Governor Response Limits flag ("base load") is used.

  cache_GateCommand := local_gv;

  cache_LastTimeStepGateCommand := local_gv;

  cache_BC := fB_GV.XtoY(local_gv);

  cache_GV := local_gv;

  cache_BB := cache_BC;

  cache_BH := cache_BC;

  cache_AB := (fbgvmin + (1-fbgvmin)*cache_BB);

  cache_AF := cache_AB * local_gv;

  cache_Hscroll := GOVERNOR_DivideAndSquareForHead(local_q, cache_af, fHdam);

 

  If fblb <> 0 Then fBackLash_blb := TTxBacklash.CreateBackLash(self,fblb,cache_BB);

  If fblg <> 0 Then fBackLash_blg := TTxBacklash.CreateBackLash(self,fblg,local_GV);

 

  StateVector[1] := Local_PElec;

  StateVector[2] := 1.0; // speed

  StateVector[4] := 0.0; // model input to derivative state as (speed - 1)

  StateVector[5] := 0.0;

  StateVector[6] := local_gv;

  StateVector[7] := cache_BC;

  StateVector[8] := cache_BC;

  StateVector[9] := local_q;

  // PIDInput = Pref - Speed - Relec*PElec - Rg*Gate

  //            PIDInput must be zero initially because we require Ki > 0

  // 1.0 here represents the initial speed

  if ffd = 0 then begin

    Pref := 1.0 + local_gv*fRg;

    StateVector[3] := local_gv;

  end

  else begin

    Pref := 1.0 + local_PElec*fRe;

    StateVector[3] := local_gv - fKp*(Pref - 1.0);

  end;

  cache_Spref := Pref;

 

  // Set ignored states (this is a boolean vector PowerWorld uses to signify ignored states)

  if fInvtpe = 0 then IgnoreStateVector[1] := True;

  if fInvtsp = 0 then IgnoreStateVector[2] := True;

  // 23 is the Ki integrator

  if fInvTd  = 0 then IgnoreStateVector[4] := True;

  if fInvtg  = 0 then IgnoreStateVector[5] := True;

  // 56 is the gate integrator

  if fInvtbd = 0 then IgnoreStateVector[7] := True;

  if fInvtbs = 0 then IgnoreStateVector[8] := True;

  // 89 is the water integrator

end;

 

function LOCAL_BackSolveForGate(local_af : double) : double;

  var i : integer;

      local_gk, local_gm, local_bk, local_bm,

      local_slope,

      local_A, local_B, local_C : double;

  begin

    Result := 0;

    i := fB_GV.Count;

    if i = 0 then begin       // just assume Bgv = 1.0 always, which means that

      result := local_af;

      exit;

    end;

    if i = 1 then begin

      local_bk := fB_GV.Y(1);

      result := local_af/( fbgvmin + local_bk*(1-fbgvmin) );

      exit;

    end;

    while i >= 0 do begin

      local_gk := fB_GV.X(i);

      local_bk := fB_GV.Y(i);  

      if local_af < local_gk*( fbgvmin + local_bk*(1-fbgvmin) ) then begin // just keep going

        if i = 1 then begin              // However if i = 1, this is degenerate case!

         result := local_af/( fbgvmin + local_bk*(1-fbgvmin) );

          exit;

        end;

      end

      else begin

        if (i = fB_GV.Count) then begin

          result := local_af/( fbgvmin + local_bk*(1-fbgvmin) ); // just use this last Bk value

          exit;

        end

        else begin

          local_gm := fB_GV.X(i+1);

          local_bm := fB_GV.Y(i+1);

          local_slope := (local_bm - local_bk)/(local_gm - local_gk);

          if abs(local_Slope) > 1E-6 then begin

            {

             we are trying to solve for gv given the value of af.

                 af = gv * [ bgvmin + (1-bgvmin)*Bgv ]

             Solve this for Bgv to make it easier for next step and we have

                       af/gv - bgvmin

                 Bgv = --------------

                         1 - bgvmin

             If we're one of the line segments of the Bgv vs Gv curve then we have

             a line segement going from (gk, bk) sloping up to (gm, bm)

                                      (bm-bk)

                 Bgv = bk + (gv-gk) * -------

                                      (gm-gk)

           Now equate these two function for Bgv and solve for gv  (Note | just grouping stuff)

                     1    |   -af    |    |  bgvmin               (bm-bk)|        |(bm-bk)|

                0 = --- * |--------- |  + |---------- + bk - gk * -------| + gv * |-------|

                    gv    |(1-bgvmin)|    |(1-bgvmin)             (gm-gk)|        |(gm-gk)|

             Now, multiply through by gv and make terms for "A, B, C" for quadratic function

                0 = C + B*gv + C*sqr(gv)  }

            local_C := -local_AF/(1-fbgvmin);

            local_B := fbgvmin/(1-fbgvmin) + local_bk - local_gk*local_slope;

            local_A := local_Slope;

            result := (- local_B + sqrt( sqr(local_B) - 4*local_A*local_C))/ (2*local_A);

            exit;

          end

          else begin

            {

            We're on a slope with constant Bk, so back to  af = gv * [ bgvmin + (1-bgvmin)*Bgv ]

            Which can be solved as                         gv = af/bgvmin + bk*(1-bgvmin)

            }

            result := local_af/( fbgvmin + local_bk*(1-fbgvmin) );

            exit;

          end;

        end;

      end;

      i := i - 1;

    end;

  end;

 

function LOCAL_BackSolveForQ(local_afmax, local_Pmech : double; var local_q : double) : boolean;

      {

This function was added in September 2022 to handle situation where the maximum gate

Value is not enough to achieve the af value necessary to get Pmech desired. 

We will again solve this by increasing the Hdam value

 

       Solving Equations: sqr(q/afmax) = Hdam  and  P(q)*Hdam = Pmech

       Substitute first equation into the second one -->   P(q)*sqr(q/afmax) = Pmech

          P(q)*sqr(q) = Pmech*sqr(afmax)

          P(q)*sqr(q) - Pmech*sqr(afmax) = 0

 

       If P(q) = q  (meaning we have piecewise linear function at all this degenerate solution is

          q * sqr(q/afmax) = Pmech --> q = (Pmech*sqr(afmax)) ^ (1/3)

 

       Otherwise, we have only 1 point (or we end up on a horizontal segment), then this mean that P(q) is a constant

       If P(q) = Pk (1 point, or we have a zero slope on this segment)

          Pk * sqr(q/afmax) = Pmech --> q = sqrt(Pmech/Pk)*afmax

 

       Otherwise we're looking at somewhere between 2 points

       Assume we're on line segment between (qk, Pk) and (qm, Pm), so we can write

                               (Pm-Pk)

          P(q) = Pk + (q-qk) * -------

                               (qm-qk)

                      (Pm-Pk)             (Pm-Pk)

          P(q) =  q * ------- + Pk - qk * -------

                      (qm-qk)             (qm-qk)

                      (Pm-Pk)

       Define Slope = -------

                      (qm-qk)

          P(q) = q*Slope + Pk - qk*Slope

 

          P(q)*sqr(q) - Pmech*sqr(afmax) = 0

          (q*slope + Pk - qk*Slope)*sqr(q) - Pmech*sqr(afmax) = 0

          [Slope]*q^3 + [Pk - qk*Slope]*q^2 + [- Pmech*sqr(afmax)] = 0;

 

          Slope = (Pm-Pk)/(qm-qk)

          A     = Slope              // A > 0 (bad user input otherwise)

          B     = Pk - qk*Slope      // B can be positive or negative

          D     = -Pmech*sqr(afmax)  // D < 0 (Pmech can’t be negative!)

 

       By assuming Slope > 0 this means that we have 1 sign change when looking through the

       Polynomial coefficients, so by Descartes sign rule, we have exactly 1 positive real root

 

       Degenerate situation when no P vs Q curve exists. In this situation P(q) = q always

       (multiplier is just 1.00)

          P(q)*sqr(q) - Pmech*sqr(afmax) = 0

          q^3 = Pmech*sqr(afmax)

          q = ( Pmech*sqr(afmax) ) ^(1/3) // cube root

 

       Degenerate situation when Slope = 0, then this is

                A=0; B=Pk; C=0; D=-Pmech*sqr(afmax)

                Pk*sqr(q) = Pmech*sqr(afmax)

          Solution is then

                q = sqrt(Pmech/Pk)*afmax

      }

 

    procedure LOCAL_HandlePkConstant(local_Pk: double);

    begin

      if local_Pk < 0.0001 then local_Pk := 0.0001; // this should never happen!

      Result := true;

      Local_q := sqrt(local_Pmech/local_Pk) * local_afmax;

    end;

 

  var i : integer;

      local_qk, local_qm, local_Pk, local_Pm,

      _A, _B, _D, local_slope, _Pmech_sqrAfmax : double;

begin

    result := false;

    _Pmech_sqrAfmax := local_Pmech*sqr(local_afmax);

    i := fP_Q.Count;

    if i = 0 then begin

      result := true;

      local_q := GOVERNOR_CubeRoot(_Pmech_sqrAfmax);

      exit;

    end;

    if i = 1 then begin

      local_Pk := fP_Q.Y(1);

      LOCAL_HandlePkConstant(local_Pk);

     exit;

    end;

    Result := 0;

   while i >= 0 do begin

      local_qk := fP_Q.X(i);

      local_Pk := fP_Q.Y(i);

      if sqr(local_qk)*local_Pk > _Pmech_sqrAfmax then begin

        // just keep going normally here,       

        if i = 1 then begin // However if i = 1, this is silly case!

          LOCAL_HandlePkConstant(local_Pk);

          exit;

        end;

      end

      else begin

        if (i = fP_Q.Count) then begin

          LOCAL_HandlePkConstant(local_Pk);

       end

        else begin

          local_qm := fP_Q.X(i+1);

          local_Pm := fP_Q.Y(i+1);

          local_slope := (local_Pm - local_Pk)/(local_qm - local_qk);

          if abs(local_Slope) < 1E-6 then begin

            LOCAL_HandlePkConstant(local_Pk);           

          end

          else if local_Slope > 0 then begin // Solving A*q^3 + B*q^2 + D = 0

            _A := local_Slope;                     // must be positive

            _B := local_Pk - local_qk*local_Slope; // Could by pos or neg

            _D := -_Pmech_sqrAfmax;                // must be negative

            // Because A>0 and D<0, then there is exactly 1 sign change

            // By Descartes Rule of Signs, this means there is ONE positive answer

            result := true;            

            Local_q := SolveCubicAndReturnPositiveRealAnswer(_A,_B,0,_D);

          end;

        end;

        Exit; // exit no matter what here.  If a local_Slope < 0, don’t do anything

      end;

      i := i - 1;

    end;

  end;

 

Derivative Function

  procedure LOCAL_HandleNonWindup(theStateOffset : integer; theDeriv, themax, themin : double);

  var local_s : double;

  begin

    local_s := StateVector[theStateOffset];

    if ( local_s >  themax) then StateVector[theStateOffset] := themax;

    if ( local_s <  themin) then StateVector[theStateOffset] := themin;

    Derivative[theStateOffset] := theDeriv;

    if ( local_s >= themax) and ( Derivative[theStateOffset] > 0 ) then

     Derivative[theStateOffset] := 0;

    if ( local_s <= themin) and ( Derivative[theStateOffset] < 0 ) then

      Derivative[theStateOffset] := 0;

  end;

 

var local_Pelec,

    local_Speed,

    local_PropIn,

    local_IntIn,

    local_SpeedError : double;

    local_Deriv : double;

Begin

  local_Pelec := PElec*GenObject.MVABase/fTrate;

  if finvTsp < 0 then local_Speed := GenObject.GetBusFreqPU // bus frequency

  else local_Speed := actualWPU; // rotor speed

  If IgnoreStateVector[1] Then StateVector[1] := local_Pelec;

  If IgnoreStateVector[2] Then StateVector[2] := local_Speed;

  If IgnoreStateVector[4] Then StateVector[4] := StateVector[1] - 1.0;

  Derivative[2] := abs(finvTsp)*(local_Speed - StateVector[2]);

  Derivative[4] := finvTd*(StateVector[2] - 1.0 - StateVector[4]);

 

  local_SpeedError := cache_Spref - StateVector[2] + GenObject.Paux/GetTRate; // AAA 03/13/20

  if fFD = 0 then begin

    Derivative[1] := 0;

    // proportional control DOES include gate droop when FD = 0

    local_PropIn := local_SpeedError - fRg*cache_LastTimeStepGateCommand;

    local_IntIn := local_PropIn;

  end

  else begin

    Derivative[1] := finvTpe*(local_Pelec - StateVector[1]);

    // proportional control DOES NOT include Pelec droop term when FD = 1

    local_PropIn := local_SpeedError;

    local_IntIn := local_SpeedError - fRe*StateVector[1];

  end;

  LOCAL_HandleNonWindup(3, fKi*local_IntIn, fgmax - local_PropIn*fKp, fgmin - local_PropIn*fKp);

  cache_GateCommand := fKp*local_PropIn + StateVector[3]; // proportional + Integrator

  // Derivative block effect

  If not IgnoreStateVector[4] Then begin

    cache_GateCommand := cache_GateCommand -

                         fKd*finvTd*(StateVector[2] - 1.0 - StateVector[4]);

  end;

  if cache_GateCommand > fGmax then cache_GateCommand := fgmax;

  if cache_GateCommand < fgmin then cache_GateCommand := fgmin;

 

  local_Deriv := fInvTg*( fKg *(cache_GateCommand - StateVector[6]) - StateVector[5] );

  LOCAL_HandleNonWindup(5, local_Deriv, fvelm, -fvelm);

  LOCAL_HandleNonWindup(6, StateVector[5], fgmax, fgmin);

 

  // gate buffer

  if (StateVector[6] < fbuf) AND (Derivative[6] < -fbuv) then Derivative[6] := -fbuv;

  // handle gate backlash

  cache_gv := StateVector[6];

  if fBacklash_blg <> nil then cache_gv := fBacklash_blg.output( cache_gv );

 

  cache_BC := fB_GV.XtoY(cache_GateCommand);

  if ( fInvtbd > 0 ) then begin

    local_Deriv := cache_BC - StateVector[7];

    if      ( local_Deriv >  fdbbd ) then local_Deriv := local_Deriv - fdbbd

    else if ( local_Deriv < -fdbbd ) then local_Deriv := local_Deriv + fdbbd;

    Derivative[7] := finvTbd * local_Deriv;

    cache_bh := StateVector[7];

  end

  else begin

    StateVector[7] := cache_bc;

    Derivative[7] := 0;

    // note this won't always update the bh value!

    // That's fine, this is hysterisis.  It only moves once the deviation is large enough

    if (cache_bc - fdbbd) > cache_bh then cache_bh := cache_bc - fdbbd;

    if (cache_bc + fdbbd) < cache_bh then cache_bh := cache_bc + fdbbd;

  end;

 

  if finvTbs > 0 then begin

    local_Deriv := cache_bh - StateVector[78];

    if      ( local_Deriv >  fdbbs ) then local_Deriv := local_Deriv - fdbbs

    else if ( local_Deriv < -fdbbs ) then local_Deriv := local_Deriv + fdbbs;

    local_Deriv := finvTbs * local_Deriv;

    if      local_Deriv > +fblv then local_Deriv := +fblv

    else if local_Deriv < -fblv then local_Deriv := -fblv;

    Derivative[8] := local_Deriv;

  end

  else begin

    StateVector[8] := cache_bh;

    Derivative[8] := 0;

  end;

 

  cache_bb := StateVector[8];

  if fBacklash_blb <> nil then cache_bb := fBacklash_blb.output( cache_bb );

  cache_ab := fbgvmin + (1 - fbgvmin)*cache_bb;

  cache_af := cache_ab * cache_gv;

  // when cache_af value input to water dynamics is an extremely small number,

  // the dynamics can become extremely fast because we divide by cache_af.

  // Model starts entering a region we have have 0/0 as Q value also goes to zero.

  // Model these dynamics as algebraic and instantly change the state value to handle this.

  // Otherwise numerical problems related to 0/0 will result

  if cache_af < 0.005 then StateVector[9] := sqrt(fHdam)*cache_af;

  cache_Hscroll := sqr(StateVector[9]/cache_af);

 

  // Don’t allow the water flow to drop below 0.0001 per unit (more avoid 0/0 situations)

LOCAL_HandleNonWindup(9, finvTw*( fHdam - cache_hscroll ), 1E10, 0.0001);

end;