Exciter Model: ST4C

 

Model Equations and/or Block Diagrams

Parameters:

VOS PSS input: if = 1, add to error signal; if = 2, add after HV gate 1
OEL OEL input: if < 2, add to error signal; if = 2, LV gate 1; if = 3, LV gate 2
UEL UEL input: if < 2, add to error signal; if = 2, HV gate 1; if = 3, HV gate 2
SCL SCL input: if < 2, add to error signal; if = 2, Take Over 2 1; if = 3, Take Over 3
SW1 Logical switch 1 (1 = Position A, 2 = Position B)
Tr Filter time constant, sec
Kpr Proportional gain, pu
Kir Integral gain, pu
Vrmax Maximum control element output, pu
Vrmin Minimum control element output, pu
Kpm Proportional gain of field voltage regulator, pu
Kim Integral gain of field voltage regulator, pu
VmMax Model Parameters\VmMax
VmMin Model Parameters\VmMin
Ta Voltage regulator time constant, sec
VaMax Maximum exciter output, p.u.
VaMin Minimum exciter output, p.u.
Kg Excitation limiter gain, pu
Tg Feedback time constant of field current regulator, sec.
VgMax Maximum excitation voltage
Kp Potential source gain, pu
Ki Current source gain, pu
Xl P-bar leakage reactance, pu
ThetaPDeg Phase angle of potential source, degrees
Kc Rectifier regulation factor, pu
VbMax Maximum excitation voltage, pu