Exciter Model: ST2C
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tf < 0.5*Mult*TimeStep then Tf = 0, ElseIf 0.5*Mult*TimeStep < Tf < Mult*TimeStep then Tf = Mult*TimeStep
- If 0.0 < Te < 0.5*Mult*TimeStep then Te = 0, ElseIf 0.5*Mult*TimeStep < Te < Mult*TimeStep then Te = Mult*TimeStep
- If 0.0 < Ta < 0.5*Mult*TimeStep then Ta = 0, ElseIf 0.5*Mult*TimeStep < Ta < Mult*TimeStep then Ta = Mult*TimeStep
- If 0.0 < Tr < 0.5*Mult*TimeStep then Tr = 0, ElseIf 0.5*Mult*TimeStep < Tr < Mult*TimeStep then Tr = Mult*TimeStep
- If Ka = 0 then Ka = Mult*TimeStep
- If Vrmax < Vrmin then swap the values
- If VPImax < VPImin then swap the values
- Kpr and Kir: Kpr can't be 0 if Kir = 0, if true then Kpr changed to 40.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vr > Vrmax, then Vrmax = Vr or if Vr < Vrmin, then Vrmin = Vr
- If VPI > VPImax, then VPImax = VPI or if VPI < VPImin, then VPImin = VPI
- If Efd > Efdmax, then Efdmax= Efd
Model Equations and/or Block Diagrams
Parameters:
| OEL | OEL input: if < 2, add to error signal; if = 2, LV gate 1; if = 3, LV gate 2 |
| UEL | UEL input: if < 2, add to error signal; if = 2, HV gate 1; if = 3, HV gate 2 |
| Tr | Filter time constant, sec |
| Ka | Gain, pu |
| Ta | Voltage regulator time constant, sec |
| Vrmax | Maximum control element output, pu |
| Vrmin | Minimum control element output, pu |
| Ke | Exciter field resistance time constant, pu |
| Te | Exciter field time constant, sec |
| Kf | Rate feedback gain, pu |
| Tf | Rate feedback constant, sec |
| Kp | Potential source gain, pu |
| ThetaPDeg | Phase angle of potential source, degrees |
| Ki | Current source gain, pu |
| Xl | P-bar leakage reactance, pu |
| Kc | Rectifier regulation factor, pu |
| Efdmax | Maximum excitation output, pu |
| VbMax | Maximum excitation voltage, pu |
| Kpr | Proportional gain, pu |
| Kir | Integral gain, pu |
| Vpidmax | PID maximum limit |
| Vpidmin | PID minimum limit |