Exciter Model: EXPIC1
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tr < 0.5*Mult*TimeStep then Tr = 0, ElseIf 0.5*Mult*TimeStep < Tr < Mult*TimeStep then Tr = Mult*TimeStep
 - If 0 < Tf1 < Mult*TimeStep then Tf1 = Mult*TimeStep
 - If 0.0 < Tf2 < 0.5*Mult*TimeStep then Tf2 = 0, ElseIf 0.5*Mult*TimeStep < Tf2 < Mult*TimeStep then Tf2 = Mult*TimeStep
 - If 0.0 < Ta2 < 0.5*Mult*TimeStep then Ta2 = 0, ElseIf 0.5*Mult*TimeStep < Ta2 < Mult*TimeStep then Ta2 = Mult*TimeStep
 - If 0.0 < Ta4 < 0.5*Mult*TimeStep then Ta4 = 0, ElseIf 0.5*Mult*TimeStep < Ta4 < Mult*TimeStep then Ta4 = Mult*TimeStep
 - If Vrmax < Vrmin then swap the values
 - If Vr1 < Vr2 then swap the values
 - If Efdmax < Efdmin then swap the values
 
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Efd > Efdmax, then Efdmax = Efd limits or if Efd < Efdmin, then Efdmin = Efd
 - If Vr > Vrmax , then Vrmax = Vr limits or if Vr limits < Vrmin, then Vrmin = Vr limits
 - If Va > Vr1, then Vr1 = Va or if Va < Vr2, then Vr2 = Va
 
Model Equations and/or Block Diagrams
                    
                
Parameters:
| Tr | Transducer time constant, sec | 
| Ka | Voltage regulator gain | 
| Ta1 | Voltage regulator time constant, sec | 
| Vr1 | PI maximum limit, pu | 
| Vr2 | PI minimum limit, pu | 
| Ta2 | Voltage regulator time constant, sec | 
| Ta3 | Voltage regulator time constant, sec | 
| Ta4 | Voltage regulator time constant, sec | 
| Vrmax | Maximum control element output, pu | 
| Vrmin | Minimum control element output, pu | 
| Kf | Rate feedback gain, pu | 
| Tf1 | Feedback lead time constant, sec | 
| Tf2 | Feedback lag time constant, sec | 
| Efdmax | Maximum excitation output, pu | 
| Efdmin | Minimum excitation output, pu | 
| Ke | Exciter field resistance line slope margin, pu | 
| Te | Exciter field time constant, sec | 
| E1 | Field voltage value, 1 | 
| SE1 | Saturation factor at E1 | 
| E2 | Field voltage value, 2 | 
| SE2 | Saturation factor at E2 | 
| Kp | Potential source gain, pu | 
| Ki | Current source gain, pu | 
| Kc | Rectifier regulation factor, pu |