Exciter Model: AC5C

Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Te < Mult*TimeStep then Te = Mult*TimeStep
- If 0 < Tf1 < Mult*TimeStep then Tf2 = Mult*TimeStep
- If 0.0 < Tf2 < 0.5*Mult*TimeStep then Tf2 = 0, ElseIf 0.5*Mult*TimeStep < Tf2 < Mult*TimeStep then Tf2 = Mult*TimeStep
- If 0.0 < Ta < 0.5*Mult*TimeStep then Ta = 0, ElseIf 0.5*Mult*TimeStep < Ta < Mult*TimeStep then Ta = Mult*TimeStep
- If 0.0 < Tr < 0.5*Mult*TimeStep then Tr = 0, ElseIf 0.5*Mult*TimeStep < Tr < Mult*TimeStep then Tr = Mult*TimeStep
- If Vamax < Vamin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Va > Vamax, then Vamax = Va limits or if Va < Vamin, then Vamin = Va
Model Equations and/or Block Diagrams
Parameters:
OEL | OEL input: if = 2, LV gate; if < 2, subtract from error signal |
UEL | UEL input: if = 2, HV gate; if < 2, add to error signal |
SCL | SCL input: if = 2, LV gate; if < 2, subtract from error signal |
Tr | Filter time constant, sec |
Ka | Voltage regulator gain |
Ta | Voltage regulator time constant, sec |
VaMax | Maximum control element output, pu |
VaMin | Minimum control element output, pu |
Ke | Exciter field resistance constant, pu |
Te | Exciter field time constant, sec |
Kf | Rate feedback gain, pu |
Tf1 | Feedback lag time constant, sec |
Tf2 | Feedback lag time constant, sec |
Tf3 | Feedback lead time constant, sec |
E1 | Field voltage value, 1 |
SE1 | Saturation factor at E1 |
E2 | Field voltage value, 2 |
SE2 | Saturation factor at E2 |
Kc | Rectifier loading factor proportional to commutating reactance |
Kd | Exciter internal reactance, pu |
Vfemax | Exciter field current limit parameter, pu |
Vemin | Minimimum exciter output voltage, pu |
Spdmlt | If not zero, multiply output (Efd) by generator speed |