Exciter Model: AC2C

 

Model Equations and/or Block Diagrams

Parameters:

OEL OEL input: if = 2, LV gate; if < 2, subtract from error signal
UEL UEL input: if = 2, HV gate; if < 2, add to error signal
SCL SCL input: if = 2, LV gate; if < 2, subtract from error signal
Tr Filter time constant, sec
Tb Time constant, sec
Tc Time constant, sec
Ka Voltage regulator gain
Ta Voltage regulator time constant, sec
VaMax Maximum control element output, pu
VaMin Minimum control element output, pu
Kb Exciter field current controller gain, pu
Eefmax Maximum exciter field voltage, pi
Eefmin Minimum exciter field voltage, pi
Te Exciter field time constant, sec
Vfemax Exciter field current limit parameter, pu
Kh Exciter field current feedback gain, pu
Kf Rate feedback gain, pu
Tf Rate feedback constant, sec
Kc Rectifier loading factor proportional to commutating reactance
Kd Exciter internal reactance, pu
Ke Exciter field resistance constant, pu
E1 Field voltage value, 1
SE1 Saturation factor at E1
E2 Field voltage value, 2
SE2 Saturation factor at E2
Vemin Minimimum exciter output voltage, pu
Spdmlt If not zero, multiply output (Efd) by generator speed