Time Step Simulation: Results Constraints

Concept Link IconSee Also

 

The Results Constraints page of the Time Step Simulation dialog is used to convey results that are specific to an optimal power flow type of study. This page is only available with the OPF and SCOPF add-ons of Simulator. When the OPF solution type is used to solve a time point, the status of the system during that particular time is optimized so that the total operating cost of the system is minimized, and the normal operation constraints are enforced. In addition, the SCOPF solution type enforces contingency constraints. The OPF and SCOPF solutions contain information about the elements that determine the LMPs, the binding constraints, the violating contingencies, and changes in the control settings.

The information related to contingencies on these pages is available only in the SCOPF Simulator add-on.

The pages of the Results: Constraints page are:

 

Results Summary

This page is similar to the Summary Page, except that it contains additional operating information such as:

Initial Cost

The cost of operating the system given the initial generator set points and a standard power flow solution. No controls are moved to minimize cost.

Unconstrained Cost

The total operating cost after the controls are moved to minimize cost, without enforcing any normal operation or contingency constraint. The result is an operating cost that corresponds to an Economic Dispatch solution.

Unconstrained LMP

The average marginal price of the system under unconstrained optimization.

Final Cost

The total operating cost after a constrained (OPF or SCOPF) solution has been obtained.

LMP

(Average, Standard Deviation, Minimum and Maximum): Metrics of the LMP values.

Binding Lines

Number of transmission lines and transformers that are binding after the OPF/SCOPF solution has been determined.

# CTGs Unsolvable

Number of unsolvable contingencies. These are severe contingencies that would cause the power flow solution to fail for that particular time point scenario. Unsolvability of the power flow case is related to maximum loadability conditions.

You can access the details of the binding elements by right-clicking and selecting Show Binding Constraint Dialog on the local menu.

 

Binding Lines

This is a matrix grid that shows information for transmission lines and transformers that become binding constraints during the OPF or SCOPF solutions. A similar page is available for binding interfaces.

When transmission lines or transformer thermal ratings become binding constraints for a time point, a column is automatically added, forming in this manner the matrix grid. You can access the details of the binding line or transformer by right-clicking and selecting Show Binding Constraint Dialog on the local menu. The grid also shows the following summary columns:

Processed

Gets set to YES if the time point was correctly processed.

CTGs with Viols

Number of contingencies that presented one or more violations (violating contingencies). 

# CTGs Unsolveable

Number of unsolvable contingencies for the time point.

BC Line Viols

Number of transmission line and transformer violations that were identified in the base case.

# Line Viol

Number of transmission line and transformer thermal violations. 

Binding Lines

Number of binding lines in the OPF/SCOPF solution.

Line Unenforceable

Number of lines with unenforceable limits.

 

Binding Interfaces

This is a matrix grid that shows information for interfaces that become binding constraints during the OPF or SCOPF solutions. A similar page for lines is available.

When interfaces become binding constraints for a time point, a column is automatically added to the matrix grid. You can access the details of the binding interface by right clicking and selecting Show Binding Constraint Dialog on the local menu. The grid also shows the following summary columns:

Processed

Gets set to YES if the time point was correctly processed.

CTGs with Viols

Number of contingencies that presented violations (violating contingencies) 

# CTGs Unsolveable

Number of unsolvable contingencies for the time point.

BC Interface Viols

Number of interface violations that were identified in the base case.

# Interface Viol

Number of interface violations.

Binding Interface

Number of binding interfaces in the OPF/SCOPF solution.

Interface Unenforceable

Number of interfaces with unenforceable limits.

 

Binding Contingencies

This matrix grid shows information similar to that found on the Binding Lines and Binding Interfaces pages. Here though the data is organized by contingencies, which allows easy identification of the most severe contingencies. Each column of the matrix grid corresponds to a contingency. You can access the details of the binding element by right-clicking and selecting Show Binding Constraint Dialog on the local menu. The grid also shows the following summary columns:

Processed

Gets set to YES if the time point was correctly processed.

CTGs with Viols

Number of contingencies that presented violations (violating contingencies) .

# Line Viol

Number of transmission line and transformer thermal violations. 

Binding Lines

Number of binding lines in the OPF/SCOPF solution.

Binding Interfaces

Number of binding interfaces in the OPF/SCOPF solution.

 

Binding Line Summary Matrix

This matrix grid shows the number of time points for which a line has been binding due to each contingency. In this case, the rows correspond to binding lines, and the columns to violating contingencies. The grid also shows the following summary columns:

From Number

Binding line from bus number

To Number

Binding line to bus number

Circuit

Binding line circuit ID

Total Hrs

Total number of time points for which the line was binding (in the overall simulation).

Total Hrs Unenforceable

Total number of time points for which the line constraint was unenforceable (in the overall simulation).

 

Binding Line Summary List

Shows information similar to the Binding Line Summary Matrix but in form of a list. The same line may appear several times under different contingencies. Besides the information on the Binding Line Summary Matrix, this grid shows the following fields:

Contingency Name

Contingency that causes the line constraint to be binding

Avg MC

Time Average MVA Marginal Cost  

Max MC

Time Maximum MVA Marginal Cost

Min MC

Time Minimum MVA Marginal Cost