Software Patches

April 19, 2016

Bug Fixes

  • Auxiliary Files (SCRIPT and DATA Sections): Fixed bug with the ReassignIDs(objecttype, field, filter, UseRight) script command so that the UseRight parameter actually works.
  • Auxiliary Files (SCRIPT and DATA Sections): Fixed bug saving out aux files with objects using three-winding transformers that do not have a tertiary winding.
  • General: Fixed calculation of integer tap position field for phase shifter. It was being calculated based on transformer tap instead of phase.
  • Integrated Topology Processing (ITP): Fixed error when saving a Consolidated Case if switched shunts were modeled across open breakers. Simulator now automatically moves these shunts across the open breaker to be grouped with other shunts on the same Superbus, however these shunts were not being properly set to Status=OPEN when doing this.
  • Transient Stability: Added ability to read/write the REPC_B model from the DYD file format.