Stabilizer Model: WTGPT_A and WTPTA1
AutoCorrection Properties
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0 < Tp < Mult*TimeStep then Tp = Mult*TimeStep
- If RThetaMax < RThetaMin then swap the values. If RThetaMax < 0 then RThetaMax change sign to positive. If RThetaMin > 0 then change sign to negative.
- If ThetaMax < ThetaMin then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters for WTGPT_A:
Tp | Blade response time constant, sec |
Kpp | Pitch control porportional gain, deg/pu-speed |
Kip | Pitch control integral gain, deg/pu speed-sec |
Kpc | Pitch compensator proportional gain, deg./pu P |
Kic | Pitch compensator integral gain, deg/pu P-sec |
ThetaMin | Minimum pitch, deg |
ThetaMax | Maximum pitch, deg |
RThetaMin | Pitch rate limit negative, deg/sec |
RThetaMax | Pitch rate limit, deg/sec |
Kcc | Cross Proportional Gain |
MVABase | MVABase: MVABase for the object parameters |
Parameters for WTPTA1:
Kiw | Pitch control integral gain, deg/pu speed-sec |
Kpw | Pitch control porportional gain, deg/pu-speed |
Kic | Pitch compensator integral gain, deg/pu P-sec |
Kpc | Pitch compensator proportional gain, deg./pu P |
Kcc | Cross Proportional Gain |
Tp | Blade response time constant, sec |
ThetaMax | Maximum pitch, deg |
ThetaMin | Minimum pitch, deg |
RThetaMax | Pitch rate limit, deg/sec |
RThetaMin | Pitch rate limit negative, deg/sec |