Machine Model: GENROU

Following checks and corrections are applied during Validation and AutoCorrection.
- If Xdp > Xd then Xdp = 0.8*Xd
- If Xdpp > Minimum(Xdp, Xqp) then Xdpp = 0.8*Minimum(Xdp, Xqp)
- If Xdpp < 0.05 then Xdpp = 0.05
- If Xqp > Xq then Xqp = Xq
- If Xl >Xdpp then Xl = 0.8*Xdpp
Model Equations and/or Block Diagrams
Parameters:
H | Inertia constant, sec |
D | Damping factor, pu |
Ra | Stator resistance, pu |
Xd | Direct axis synchronous reactance |
Xq | Quadrature axis synchronous reactance |
Xdp | Direct axis transient reactance |
Xqp | Quadrature axis transient reactance |
Xdpp | Direct axis subtransient reactance |
Xl | Stator leakage reactance |
Tdop | Open circuit direct axis transient time constant |
Tqop | Quadrature axis transient time constant |
Tdopp | Open circuit direct axis subtransient time constant |
Tqopp | Quadrature axis subtransient time constant |
S1 | Saturation factor at 1.0 pu flux |
S12 | Saturation factor at 1.2 pu flux |
RComp | Compensating resistance for voltage control, pu |
XComp | Compensating reactance for voltage control, pu |