Branch Model: ZDCB
To be documented.
Model Equations and/or Block Diagrams
Parameters:
| NoTrip | No Trip Flag. Set to > 0 to disable breaker tripping. Note: relay signal will still update. |
| Shape1 | Shape of Impedance Zone 1. 0 means a circle, lens or tomato. 1 means a rectangle |
| Shape2_Relay | Shape of Relay End Impedance Zone 2. 0 means a circle, lens or tomato. 1 means a rectangle |
| Shape2_Other | Shape of Other End Impedance Zone 2. 0 means a circle, lens or tomato. 1 means a rectangle |
| Shape3_Relay | Shape of Relay End Impedance Zone 3. 0 means a circle, lens or tomato. 1 means a rectangle |
| Shape3_Other | Shape of Other End Impedance Zone 3. 0 means a circle, lens or tomato. 1 means a rectangle |
| Tcb | Breaker Operating Time (in Seconds) |
| Ang1 | Angle (in degrees) of Impedance Zone 1 |
| Rf1 | Forward Reach Impedance (in per unit) of Impedance Zone 1 |
| Rr1 | Reverse Reach Impedance (in per unit) of Impedance Zone 1. (Note: For backward reach, specify a POSITIVE number.) |
| Wt1 | Total Width (in per unit) of Impedance Zone 1. If Width > Rf + Rr, then use union of circles (tomato). If Width < Rf + Rr, then use intersection of circles (lens). If Width = 0 or Rf + Rr, then just use one circle (circle). |
| Wr1 | Right Width (in per unit) of Impedance Zone 1. (Only used for rectangular shape) |
| T1 | Pickup Time (in Seconds) of Impedance Zone 1 |
| Ang2_Relay | Angle (in degrees) of Relay End Impedance Zone 2 |
| Rf2_Relay | Forward Reach Impedance (in per unit) of Relay End Impedance Zone 2 |
| Rr2_Relay | Reverse Reach Impedance (in per unit) of Relay End Impedance Zone 2. (Note: For backward reach, specify a POSITIVE number.) |
| Wt2_Relay | Total Width (in per unit) of Relay End Impedance Zone 2. If Width > Rf + Rr, then use union of circles (tomato). If Width < Rf + Rr, then use intersection of circles (lens). If Width = 0 or Rf + Rr, then just use one circle (circle). |
| Wr2_Relay | Right Width (in per unit) of Relay End Impedance Zone 2. (Only used for rectangular shape) |
| T2_Relay | Pickup Time (in Seconds) of Relay End Impedance Zone 2 |
| Ang2_Other | Angle (in degrees) of Other End Impedance Zone 2 |
| Rf2_Other | Forward Reach Impedance (in per unit) of Other End Impedance Zone 2 |
| Rr2_Other | Reverse Reach Impedance (in per unit) of Other End Impedance Zone 2. (Note: For backward reach, specify a POSITIVE number.) |
| Wt2_Other | Total Width (in per unit) of Other End Impedance Zone 2. If Width > Rf + Rr, then use union of circles (tomato). If Width < Rf + Rr, then use intersection of circles (lens). If Width = 0 or Rf + Rr, then just use one circle (circle). |
| Wr2_Other | Right Width (in per unit) of Other End Impedance Zone 2. (Only used for rectangular shape) |
| T2_Other | Pickup Time (in Seconds) of Other End Impedance Zone 2 |
| Ang3_Relay | Angle (in degrees) of Relay End Impedance Zone 3 |
| Rf3_Relay | Forward Reach Impedance (in per unit) of Relay End Impedance Zone 3 |
| Rr3_Relay | Reverse Reach Impedance (in per unit) of Relay End Impedance Zone 3. (Note: For backward reach, specify a POSITIVE number.) |
| Wt3_Relay | Total Width (in per unit) of Relay End Impedance Zone 3. If Width > Rf + Rr, then use union of circles (tomato). If Width < Rf + Rr, then use intersection of circles (lens). If Width = 0 or Rf + Rr, then just use one circle (circle). |
| Wr3_Relay | Right Width (in per unit) of Relay End Impedance Zone 3. (Only used for rectangular shape) |
| T3_Relay | Pickup Time (in Seconds) of Relay End Impedance Zone 3 |
| Ang3_Other | Angle (in degrees) of Other End Impedance Zone 3 |
| Rf3_Other | Forward Reach Impedance (in per unit) of Other End Impedance Zone 3 |
| Rr3_Other | Reverse Reach Impedance (in per unit) of Other End Impedance Zone 3. (Note: For backward reach, specify a POSITIVE number.) |
| Wt3_Other | Total Width (in per unit) of Other End Impedance Zone 3. If Width > Rf + Rr, then use union of circles (tomato). If Width < Rf + Rr, then use intersection of circles (lens). If Width = 0 or Rf + Rr, then just use one circle (circle). |
| Wr3_Other | Right Width (in per unit) of Other End Impedance Zone 3. (Only used for rectangular shape) |
| T3_Other | Pickup Time (in Seconds) of Other End Impedance Zone 3 |