Contingency Options: Injection Group
These features were added in Version 24.
The Injection Group Post-Contingency Response display can be opened from the Modeling group of the Contingency Analysis dialog Options page. This display provides a specialized InjectionGroup display with specific fields used for setting the post-contingency response of individual injection Groups.
|
Field |
Description |
|
CTGOutageIntertie |
This field is a string field containing the identifying string for either a Branch or Interface object using the syntax for of Object ID as described in ObjectID Field for use in Auxiliary Files. For example, the string may be "Branch 234 143 AB" for a transmission line or "Interface 'MyName'" .
The use of this field is described in detail in Running the Contingency Analysis. Generally, if the InjectionGroup has some online generation, load, or shunt objects in the reference case and actions during the contingencies cause all of the devices in the InjectionGroup to be opened, then the branch or interface defined by the CTGOutageIntertie will also be opened. When using an interface, this means that all the AC Branches in the interface will be opened. |